There are two nos of 33Kv/11Kv 5MVA transformers conecting
through HT cable from substation having metering at
substation itself.One transformer used at a time another
remains stand by.Further 11 nos of 11Kv/440V transformers
are attached on it and each transformer is having its own
Power factor correction panel.Now one 33/11Kv transformer
at no load condition/Stand by condition is having power
factor in leading side upto 0.21 and while when another
tranformer at same situation have power factor in lagging
0.42. Now one thing is clear that transformer one is having
1.5 Km long 33kv cable due to that PF goes in leading side
and another is having only 250 mtr length remains him
lagging. Now i want to know that how i can maintain the
Power factor at no load/ stand by position though both are
behaving in seperate manner.
Answer Posted / k.prakashchandra
Pf at no load is not to be heeded ,as the magnetizing
current is very low and the ct may not measure it accurately
wrt both magnitude and angle shift
| Is This Answer Correct ? | 4 Yes | 2 No |
Post New Answer View All Answers
what is DRP panels?
what happens if dc supply is given and the remedies for it.
write a program that prints prime numbers from 1-20 in digonal form
WHAT IS THE USE OF PIG TAIL IN WINDOW CT ?
How can calculate the earthing strip of Copper/GI for rating of 30kV,discharge current 10KA Lightning arrester.
Why the symbol of register is "zig zag"
If we need 4c× 50mm sq cable but it's not available so we can pull 4c×25mm sq two cables?
What do you mean by an instrument transformer?
What do you mean by phasors?
explain types of electric welding and its applications
how much cable size required for 70 kilowatt load.
How is operate breaker failure scheme in substation
what are the Alarm, Trip & Safety equipment (Issues) present in Power Transformers pls Mail it to ashokbabunhce@gmail.com
working principle of oil startar
Define de-sensitivity?