There are two nos of 33Kv/11Kv 5MVA transformers conecting
through HT cable from substation having metering at
substation itself.One transformer used at a time another
remains stand by.Further 11 nos of 11Kv/440V transformers
are attached on it and each transformer is having its own
Power factor correction panel.Now one 33/11Kv transformer
at no load condition/Stand by condition is having power
factor in leading side upto 0.21 and while when another
tranformer at same situation have power factor in lagging
0.42. Now one thing is clear that transformer one is having
1.5 Km long 33kv cable due to that PF goes in leading side
and another is having only 250 mtr length remains him
lagging. Now i want to know that how i can maintain the
Power factor at no load/ stand by position though both are
behaving in seperate manner.
Answer Posted / k.prakashchandra
Pf at no load is not to be heeded ,as the magnetizing
current is very low and the ct may not measure it accurately
wrt both magnitude and angle shift
Is This Answer Correct ? | 4 Yes | 2 No |
Post New Answer View All Answers
what is the effect of un-synchronized power.
In TNC switch, is there any 1NO+1NC block ? and if we move over closing position, is ther any affect on trip position or vice versa?
for 4 MVA , 33K.V/6.6K.V transformer. secondary side the connected load is 3000H.P. What is the rating of capacitor bank to be insttaled.
WHAT IS THE DIFFERENE IN ACTION OF MCB,MCCB,RCCB
if 12v battery get discharged for 2 months after if we put charge it will charge again?how much time it will take to charge?
In Plumbing services What are accessories we consider for a bathroom?
what is power factor ? how we can calculate the low power factor and amount of capacitor for improve that low factor ?
what is the minimum voltage require to injure our body?
what is the vvvf in the dumbwaiter?? or lift. what is the actual process?/
what is mean by PIR in circuitbreaker and give me detail of that?
why the arc welding machines require parallel earthing systems? ie why each machines are connected to earth pit by separate wires during earthing? wats it adavantages?
I HAVE A 50A MCCB AS PER DESIGN LINE WIRE CONNECT UPWORD SIDE AND LOAD IS CONNECTED TO DOWNWARD SIDE TO THE MCCB.IF NOW ANY ONE CHANGE SUPPLY & LOAD(WISEVERSA) WHAT HAPPENS ? DOES MCCB OPERATION OR WORKING FUNCTION NORMAL IF YES THAN WHY THERE ARE MARKED LINE & LOAD ON MCCB.
what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?
What is star-delta transformer?
how works inductive &capacitive sensors?