There are two nos of 33Kv/11Kv 5MVA transformers conecting
through HT cable from substation having metering at
substation itself.One transformer used at a time another
remains stand by.Further 11 nos of 11Kv/440V transformers
are attached on it and each transformer is having its own
Power factor correction panel.Now one 33/11Kv transformer
at no load condition/Stand by condition is having power
factor in leading side upto 0.21 and while when another
tranformer at same situation have power factor in lagging
0.42. Now one thing is clear that transformer one is having
1.5 Km long 33kv cable due to that PF goes in leading side
and another is having only 250 mtr length remains him
lagging. Now i want to know that how i can maintain the
Power factor at no load/ stand by position though both are
behaving in seperate manner.

Answer Posted / k.prakashchandra

Pf at no load is not to be heeded ,as the magnetizing
current is very low and the ct may not measure it accurately
wrt both magnitude and angle shift

Is This Answer Correct ?    4 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the effect of un-synchronized power.

1553


In TNC switch, is there any 1NO+1NC block ? and if we move over closing position, is ther any affect on trip position or vice versa?

1763


for 4 MVA , 33K.V/6.6K.V transformer. secondary side the connected load is 3000H.P. What is the rating of capacitor bank to be insttaled.

2153


WHAT IS THE DIFFERENE IN ACTION OF MCB,MCCB,RCCB

1961


if 12v battery get discharged for 2 months after if we put charge it will charge again?how much time it will take to charge?

1529






In Plumbing services What are accessories we consider for a bathroom?

1556


what is power factor ? how we can calculate the low power factor and amount of capacitor for improve that low factor ?

1095


what is the minimum voltage require to injure our body?

5677


what is the vvvf in the dumbwaiter?? or lift. what is the actual process?/

1620


what is mean by PIR in circuitbreaker and give me detail of that?

3101


why the arc welding machines require parallel earthing systems? ie why each machines are connected to earth pit by separate wires during earthing? wats it adavantages?

1740


I HAVE A 50A MCCB AS PER DESIGN LINE WIRE CONNECT UPWORD SIDE AND LOAD IS CONNECTED TO DOWNWARD SIDE TO THE MCCB.IF NOW ANY ONE CHANGE SUPPLY & LOAD(WISEVERSA) WHAT HAPPENS ? DOES MCCB OPERATION OR WORKING FUNCTION NORMAL IF YES THAN WHY THERE ARE MARKED LINE & LOAD ON MCCB.

1933


what should be the no load current for 3 phase ac motors ranging from 5 kw to 1000kw?

1383


What is star-delta transformer?

695


how works inductive &capacitive sensors?

1542