Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

is KVAR (not reverse power) relay necessary to protect from
excitor field failure on a brushless, synchroneus generator?
Some people with previos experince tell me no but the
manufacturers tell me it is designed for that purpose.
Is it that it is only necessary for brushless generators
and not the older style with the slip rings and brushes?

Answer Posted / k.prakashchandra

Field failure makes synch gen run as induction gen drawing
large lagging KVAR from system and hence KVAR relay will
act.In older gen, there was no such relay.If the field
breaker tripped the whole unit tripped on master trip.If the
FB did not trip,the unit cb tripped on over current.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how much excitation voltage required to generate 1mw power?

1986


Explain the operation principle, advantages and disadvantages of the following converters: a) A 12 pulse converter b) A Switch-mode inverter c) A thyristor inverter

1963


what are the industrail measures to over ferranti effect? how would the ferranti effect the power system if those remedial mearsure arent taken? how often does this effect occurs in real power system?

2083


what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero

2209


could anybody able 2 send me jindal steels previous papers fr electrical steam....pls send 2 my id if possible....sirisha.shaik@gmail.com

2028


WHAT ARE THE CHARACTERISTICS OF AN VOLTAG AMPLIFIER

1973


Why we do 2 types of earthing on transformer (ie:)body earthing & neutral earthing , what is function. I am going to install a oo kva transformer & 380 kva dg set what should the earthing value?

1096


What is the disadventage of gland earthing(power cable) if any. ?

2045


WHAT SHOULD BE THE BEST CURRENT RATINGS (PRIMARY / SECONDARY)FOR A CT INSTALLED AT THE INCOMING 11KV PANE? WILL IT BE CALCULATED ON THE BASES OF MAXIMUM DEMANT VALUE OR ON SUM OF ALL TRANSFORMER'S KVA? NOMALLY MAX DEMAND REPRESENT THE MAXIMUM OPERATING LOAD OF THE PLANT AND TOTAL KVA OF (SAY 5 NUMBERS TRANSFORMERS) REPRESENT THE CONNECTED LOAD. WHICH i.e. MAX DEMAND KVA OR CONNECTED KVA ARE BETTER TO USE FOR CT CURRENT CALCULATION? PLEASE ANSWER.

1850


why we have to particulary use ACB for below ratings,even available of MCB,MCCB with that range ?

2873


how make megger test for control cable like 12c x 1.5mm and what it apply voltage and test timing details.

2142


i've iocl interview.. if you know the interview process please give me information..

1929


how to operate and maintenance of 1500 kva diesel generator set

1754


what is inter connected dc generator?

2756


After doubling voltage from solar cells & use step down voltage transformer can we get high current output with low voltage.

1924