If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / syed.yaseen
dear friends,
Given kw = 375
suitable kva = 375/.8 =468.75
Future extra load consider = 20% ie.. 93.75kva
total kva = 468.75 + 93.75 = 562.5
as per company designed capacity preferred is 625kva dg set
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
Dear friends I want to design busbar for1600 kva transformer(i.e2100 amps) what are all the factors to be considered before selectinga busbar what are all the standard sizes of busbars what is the formula for finding current of copper and aluminium busbar
Why colled 440V to 3-phase supply.
What are the types of the glands and difference between single and double compression type of cable Glands.
can we choose current transformer secondary, to calculate residual flux in a power transformer, so as its saturation is close to the saturation level of power transformer?
sir, i'm preparing for hpcl exam officer trainee pls tell me how the exam ques paper pls pls
Is there any Institution for giving M-tech in Electrical engineering for those who r in service? Give the details please.
How can we select suitable capacity generator for three phase load (inductive load) and how to take study analysis in 3 three phase load system ?
Any one can explaination about calibration with rotating sub standards?
What current position are you holding in your current company?
Define transfer function?
1.4 What is meant by CT knee point voltage and how would you determine it
how many electricity poles are there and what are the names and their sizes.
What is power in wattage of 8.5 TR AC
Why compensation is necessary in feedback control system?
What range of speed can you get with the armature control method of speed control of d.c. Shunt motor?