how to connect generators in parallel and what are the
required equipment to do so?
Answer Posted / bijulal
for the two generators connected in parallel the following
conditions:
voltage of both machine will be same
frequency must be same
phase sequence must be same
the equipments are:voltmeter,ammeter,wattmeter,
synchronuscope& reverse current relay will be
used.
| Is This Answer Correct ? | 10 Yes | 3 No |
Post New Answer View All Answers
what is the ground fault relay,which purpose it will be use,clearly tell me plz
How to design the no. of ceiling fans required in 5mtr X 10 mtr X 3 Mtr hight room?
how flow current in 220 kv line to line
how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take
how generator avr give to the input?
what is harmonics? what are the factors it will depend upon
What is thresh hold value of current?
Is there a possibility to use such a treshold voltage for the NMOS part of a CMOS circuit that during the switching it will start conducting only after the PMOS part will be already closed, by this eliminating the leakedge current? Please note, I'm not asking about the well bias in standby mode, but about the "antileakedge" measures during normal operation.
sir iam a 3rd yr eee student.no core company comes for recruitment to our college.my aim is to be placed in l and t.tell me the procedures.
When the relative speed between the magnetic fields of stator and rotor does is zero under steady state operation?
why occ characteristics of generator is also called as magnatization characteristics ?
A 50Hz,4-pole,3-phase,star-connected synchronous motor has a synchronous reactance of 12ohmsper phase and negligible armature resistances.the excitation is such as to give an open-circuit voltage of 13.2kilovolt.the motor is connected to 115kilovolt, 50hertz supplying. what maximum load can be the motor torque,line current and power factor?
why we used dc supply for field in dg set
before transformer oil dielectric strenght tests are taken the oil should be allowed to settle to remove option 1 air bubbles 2 gasses 3 contamination 4 water
A mass of 1200g is accelerated at 200 cm/s2by a force. The value of the force required is:(a) 2.4N(b) 2400N(c) 240 kN(d) 0.24N