Three set (each phase contain 2 cable of 400 mmsq CU XLPE
AWA) of single core cables are connected to 11 KV motor of
14 MW & the switch gear supplay is taken from 11kv feeder &
this supplay taken from 275 KV substation. Problem is one
pair cable(L3- 2 cable ) getting very hot & gland melted
and damaged in switch gear side. the other two cable
haven't any more hot(ambient temp only & L3 haveing 95- 100
Degree C. The same problem happened in 275 KV substation
switch gear side also where the supply taken for 11 kv
switch gear. But here L2 phese cable had problem. Why it is
happening like this?. The cable having temperature
different at different location from gland side inthe case
of 11KV feeder of 275 kv substation. why ?
Answer Posted / k.prakashchandra
This happens whenever there is a loose connection or under -
sized lugs are used.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how does high earth to neutral voltage affect electronic equipment?
Either the Armoured Earthing strip of HT 3 core cable have to pass through CB CT or not , why ???
what is the importance of earthing system on the generators big capacity and small?
1.4 What is meant by CT knee point voltage and how would you determine it
What is the difference between Delta & Wye windings?
how many load we can take for lighting
what is the function of capacitor duty contactor in an capacitor panel???
If a transformer primary winding operates at 240v, the secondary at 120v and the load is 1500w & the transformer is rated at 92% efficient, what's the current flowing through the primary winding of the transformer? What is the formula for finding this?
Is a d.c.compound motor is use as a booster? how?
On what basis the the size of Lightning arrester for buildings are selected ?
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1
why electron produce magnetic field when it is in motion?
What is super thermal power plant? and how it will differ from normal thermal power plant
Do you know what is dry-out test in x'mer
difrent between vcb acb sf6 and mccb breakers