Answer Posted / binosh
pressure transmitter:
in bench calibration connect a power supply 24v.give a
250ohms as loop resistance.connect a multimeter in
milliamph mode and connect it in series.and put a
communicator across the loop.the transmitters HP&LP sides
should be in open to atmosphere.this condition the
ammeter shows 4ma and the communicator shows LRV .connect a
pressure calibrator to the HP side and LP keep it open to
atm.apply pressure as the range and go on as 25%,50%,75%and
URV.then the ammeter shows 4,8,12,16,20ma
respectivly.incase you are not getting zero,make zero trim.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
HI, can anybody give details about GAS TREATMENT PLANT CONSTRUCTION,as INSTRUMENTATION ENGINEER what are the responsibilites.what are the instruments mainly instrumentation engineer will deal with
How many interlocks at turbine? Plz explain briefly
How flow can be measured with dp?
what is IEC code in cables & how to selecting cables?
Tell me the field calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter.
if in a level tx height is given, how u calculate the ranges of the tx?
Differentiate between ultrasonic flowmeter and radar type flow meter
what is the difference between -24 : +24 & 0:24 and where it use?
give some question relative instrument fitter?
What is defferent betwen ESP &PCP PUMP .HOW IT IS WORK?
How to calibration a control valve?
which type of signal used in instrument?
applications of plc in printing and packaging?
any questions on motor and energy conversions machines?
How is work 5/2 sov?