Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If I have a motor of 1 MW with 6.6 kV, running at 35% load,
how can I save energy without reducing the load?

Answer Posted / k.prakashchandra

You can not lower the load ,capacity, and voltage. To save
energy ,you are left with only reduction of line current to
lessen the I^2R losses.The pf of motor is highest at
full ,or nearly full load.At 35% load ,the pf is less and
hence, the line current is more than required to take the
load (HP)

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I have doubt that the supply HZ (very low or high than rated ) may affect the power factor. is it true. ?

1608


Write down the name of 2 lady Bir Pratin of Bangladesh

1845


what is the chiller and working principal

2272


Sate maximum power transfer theorem?

1058


What is the difference between alternator and generator?

1246


While HT line put on to activate ACB in low tention panel VCB tripping instantly.why it happens

2042


What is the need of generator relay panel

2020


What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.

1623


Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?

4274


Zone of protection and tripping scheme of arc protection relay.

1814


what happened when we supply a dc current in dc motor?? can it worked properly?

1894


why we take movement of rotor always in counter-clockwise direction in 3-phase induction motors?

1893


What is VSCF windelectrical system?

1819


What is I to C?

2045


If the feeder rating is 7.5 kw or 10 HP star-delta feeder, MCCB is taken as 63 a, contactors-32 a, how much will be the OLR rating or which range OLR should be considered when we concern about type-2 coordination?

2266