Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

can u tell the difference between star - star transformer
and delta to delta transformer?

Answer Posted / dinesh

1. Star-Star(Y-Y) Connections.I gives line voltage &#8730;3 times
phase voltage. It is economical for small high voltage
transformers as the number of turns per phase and the amount
of insulation required is less. There is no phase shift
between primary and secondary voltages. The drawback is that
the neutral is unstable because of third harmonic component
in the exciting current.


2. Delta-Delta (&#916; - &#916; ) Connections. The arrangement is
generally used in systems which carry large currents on low
voltages and specially when continuity of service is to be
maintained even though one of the phases develops fault.
There is no phase displacement between primary and secondary
voltages. There is no distortion of flux as the third
harmonic component of magnetizing current can flow in the
delta connected primary windings without flowing in the line
wires. The conductor is required of smaller x-section as the
phase current is 1/&#8730;3 times of the line current. No
difficulty is experienced due to unbalancing of loads on the
secondary side. The disadvantages are that more insulation
is required and the voltage appearing between windings and
core will be equal to full line voltage in case of earth
fault on one phase.


(techie.dinesh@gmail.com)

Is This Answer Correct ?    3 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

draw vector diagram and +ve,zero sequence diagram of symmetrical three phase fault.

2024


why Lightening Arrester Probe sharp at Top of telecom tower.

1549


HOW TO CHECK THE VECTOR GROUP OF A TRANSFORMER YD11?

3613


EHV current carrying parts need to have smooth finish,then how can a 245kv GIS with emery finish can run so long?

1883


What are books to be referred for KPTCL exam?

3676


new 90kw motor installed so how I purchased cable ,fuse,etc please give me technic for cable selected why always capacitor delta connection

1809


do any one help me to get "C" license,, i have doubts ,,, if mediators ter pls call me,, my no is 8056640042

1422


I want to do a mini project. Now I'm studying in 6th semis tor EEE Engineering.

2146


On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?

1590


how to calculate the earth mat design in 132 kv substation yard ????

6235


how to calculate fuse rating for a motor

5643


what is zinc diffusion?

2085


WHY CBCT USE ONLY IN Y PHASE NOT OTHER PHASES

2108


how we calculate the withstansing current capacity of wires&cables?

2004


why we used dc supply for field in dg set

2380