On LPG sphere tank we used LIT for level indication.High
side port is connected to the bottom of the tank while low
side port connected to the top. I would like to know how to
fill the glycerin on its low side with two condensing pot
installed,one from top and the other one for its drain
line.Please I need your expertise...thanks
Answer Posted / sam
Hi there,
This is called a normal wet leg installation. There is no
need to change the HP and LP around when you use a SMART TX.
All SMART Tx can measure in the negative with the same
amount as in the positive. exp: -1600 to +1600mmH2O
Open your manifold vents to atmosphere and do a zero trim,
next close the equalizing valve on the manifold and open HP
line to atmosphere. Fill the LP line until both catch pots
are full and the Glycerin is running out of the top catch
pot into the line going to the top tapping point of the
vessel. At this point let the liquid in the vessel fill the
HP line. Remember to do some draining to make sure there are
no air bubbles. What you need is to have the LP completely
filled with Glycerin and the HP line filled with Vessel
liquid up to the point where the tubing connects to the
vessel(not more). Whatever the transmitter reads now(neg
value)is called an atmospheric zero value(ATM).DO NOT DO A
ZERO TRIM!!
Use this formula to calculate the LRV and the URV
LRV = ATM value + (distance from bottom tapping on the
vessel to 0% point on vessel x the sg of the vessel liquid)
URV = ATM value + (distance from bottom tapping on the
vessel to 100% point on vessel x the sg of the vessel liquid)
LRV and URV UOM must first be in mmH2O if you took these Z/S
measurements in mm. After you install them with the HART you
can change it to whatever UOM you require.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
WHAT IS THE CAM POSITION IN CONTROL VALVE POSITIONER ? WHY IT IS USED?
Explain why use mmwc unit?
how to calculate range of level transmitter?
Calibration procedure for Electro magnetic Flow meter
Galvanizing.
send me model hpcl questions pleas..........my mail id mohideen.dharvesh@gmail.com
define feed forward control loop with example and drawing?
What is three element drum level control system why its better than single element?
why Fahrenheit unit of moistur analyzer transmitter
while am calibrating Drager polytron 2IR flame gas detector occured non zero status.how can i get zero status?
can we replace a slot sensor (inductive type) with limit switch (potenial free contact / no-nc type).
key phaser where is use and work
What are the types of control valves available
How digital input and digital output 's are working in dcs
kindly sent some demo question and answer