what voltage to be select in megger for insulation
resistance testing to L.V , H.T cables,motors and
transfomer?and ohms valve should be giga ohms only or what?
Answer Posted / guest
You must know what is the voltage of your installation or
the cable. Eg. if its used for 230 v. Then you can use 250V
Megger or even 500V megger. For 440V application or cables
use 500V or 1000v megger.
For HT cables 3.3kv and above you can use 5kv megger.
Ohms value will come according to the reading. If reading
is in Megaohms or Gigaohms it will appear on the scale or
change tapping accordingly if any.
| Is This Answer Correct ? | 26 Yes | 5 No |
Post New Answer View All Answers
what is invertor supply and raw powersupply
how can maintaince the acb contactor moveing and fixing kit
What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?
how to calculate the distance relay faulty zone?pls explain?
When lag/lead/lag-lead compensation is employed?
what is the difference between linear choke and suction choke?
plz tel me syllabus and exam date 4 jr executive engg (electrical)
why output is out of phase in case of common emitter?
what are the specifications we must look at to select a relay for any capacity motor?
The D.C. spark test is applicable to single conductor cable & assemblies of insulated single conductor cables without insulation shield,metallic sheath or metalic armor?
why we use the 100% and 95% stator earth fault protection for the synchronus generator ?
how to Select Lighting arrester? What r the parameters to be considered for the selection of Lighting arrester ?
How to perform a DC resistance test In Alternator and their proceduces?
how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?
what is difference between elr and R eartl realy.