1.What do you mean by inductive and capacitive parts of an
electric circuit. 2.What do you mean by decrease of
inductane and capacitance of a network? Please dont give me
the text book answer.3. What is class X ct and its
applications?
Answer Posted / sayan
Class PS/ X CT: In balance systems of protection, CT s with
a high degree of similarity in their characteristics are
required. These requirements are met by Class PS (X) CT s.
Their performance is defined in terms of a knee-point
voltage (KPV), the magnetizing current (Imag) at the knee
point voltage or 1/2 or 1/4 the knee-point voltage, and the
resistance of the CT secondary winding corrected to 75C.
Accuracy is defined in terms of the turns ratio.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
In a voltage-controlled current source A A current booster is never used B The load is always floated C A stiff current source drives the load D The load current equals Isc
LET ME NOW MORE ABOUT icu and ics for circuit breaker. how we calculate the rating of circuit breaker and i c u and ics values
In India the supply voltage is 230 volt A.C. During the negative half cycle phase becomes neutral and neutral become phase? or what will happen during negative half cycle? how the electrons flow during positive and negative half cycle?
what is mean by parallel operation of permanent magnet generators
WHAT IS THE CURRENT CARRYING CAPACITY OF 2.5/3 CORE HI TUFF CABLE,WILL IT SAFLEY CARRY 8.6 AMPS OVER 120 METRES,CAN YOU ALSO ANSWER WITH FORMULA FOR WORKINGS OUT ,THANK YOU 3RDYR APPRENTICE.
what is ps impedance test
how to setting Load amps tripping time and extra settings for load Transformer protection relay with RMU panel using C&S model relay..?
What is DC series motor?
What is meant by stator? What is meant by rotor?
why you don not show protection and type of isolation in key single line diagram?
What is the comparison between 30mA DP RCCB and 100mA DP RCCB and can replace it against 63A MCB
A 400KVA transformer has 400 Hz frequency. If the frequency is changed to 50 Hz, then what will be the new KVA rating?
What is the effect on 3phase induction motor if current setting knob of DOL kept at minimum current?
calculate external resistance values to add to the rotor of a slip ring induction motor. STATOR- 415 V, 3 phase delta, 1100 A, 50 Hz, 1490 rpm, pf 0,86 ROTOR - 660 V, 590 A, 50 Hz. STATOR current at each steps STEP1-600A,STEP2- 800A,STEP3-1000A,STEP4-1100A.
hi i have applied for lic of india south cenrtal zonal ,hyd. i didnt get hall ticket till now.let me know how can i get form internet