what happen if i connect DYn11 and DYn1 vector group
transformer in parrallel?other things are same like votage
ration,x/r ratiob etc...
Answer Posted / doug marshall
As I understand it, the convention is counterclockwise
rotation. Therefore DYn1 means that the secondary lags the
primary by 30 degrees (Subtractive Polarity). DYn11 means
that the secondary lags the primary by 330 degrees which is
the same as secondary leads the primary by 30 degrees
(Additive Polarity). Likewise, a DYn1 when operated as a
YnD1 (Step Up), the secondary or delta leads the primary Y
by 30 degrees. Therefore two DYn1 transformers connected in
series DYn1 - DYn1, the output will lag the input by 60
degrees but YnD1 - DYn1, the first stage results in the
intermediate voltage (Delta) leads by 30 degrees and at the
last stage, there is a 30 degrees lagging phase shift so
the sum phase shift from Y - Y is 0 degrees.
| Is This Answer Correct ? | 7 Yes | 17 No |
Post New Answer View All Answers
Mention what are the types of semi-conductors?
hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E
-How do you select cable size for a given load at a given distance from source of supply. How do you find voltage drop.
Discuss the effect of sudden loading of an induction motor
which cable is used for 15 Hp monoblock pump 3phase and service wire Distance is 210 feet please tell me cable size Armaured
what is feed back and what are feed back amplifiers?
what are symmetrical and non symmetrical components in electrical installation.
what are the assumptions made in swineburne's test?
What is quadrantal symmetry?
Is there possible to Test Transformer for Overfluxing Capability. Or is there any firm who does Overfluxing Test on Transformer?
is it true there's a big difference in using Cummins or Denyo...especially power output or leakage
by what factor the starting current is used when comparing star and delta connection for motor starting?
if a 3phase 100kva distribution transformer , 400 v,50 hz, 4-wire system is loaded at 160 k.w mostly 1-phase Lighting & Airconditioning split a.c load what will be the net effect on the power system in terms of voltage, powerfactor, current , efficiency of xformer
i am trying to PSUs/govermeant jobs since last 2 years but still i m not success, plz help me.
3ph motor running with unequal kw and different pf what are the reasons