If a differential pressure transmitter is calibrated for
0~2500 mmH2o and transmits a 4~20mA dc signal. The
transmitter is placed across an orifice plate which is sized
to create 2500 mmH2o differential at 5000m3/Hr
a) what is the flow rate when the transmitter signal is
13.0mA DC?
b) what is the signal output of the transmitter when flow
rate is 2500 m3/Hr ?
Answer Posted / raju
ans a)=√(13-4/16)×5000=3750 m3/hr
b)=(2500/5000)×(2500/5000)×16+4= 8 mA
| Is This Answer Correct ? | 13 Yes | 13 No |
Post New Answer View All Answers
what is the different between deflection type measurement and null type measurement in RTD?
Square root calculation for dp flow transmitter?
How the sizing of the analog signal cable is calculate?
Why ac supply load cell is used? Can we use the dc supply load cell?
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.
How u will setup SPI(2007) on Citrix Server (Thin Client Mode)? Plz Justify?
Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com
why fuse block is not used for AI signal?
䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ
Why even multiple power supplu r used in instrumentation system?
use of split range ? where it is used ? in which control loop it is used ?
what can of fault ofently come in vibration mesurement?
How earthing can be checked????
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com