Whether the DP transmitter can be utilised in the medium of
Vaccum for the measurement of Level?
Answer Posted / sankarithi
Hi Friends i finally succeeded to take the DP transmitter
into line for the Measurement of Level which is under
vaccum. The following steps to be followed.
1. Transmitter range should be in Positive side only.
2. Transmitter HP should be connected with the Level
chamber bottom side and maintain very less gap between
Level Chamber and Trasmitter HP end.
3. Connect Transmitter LP end with the Level Chamber Top
End and elevate the Pipe line 11/2 mtr above the tank level
in order to ensure that there will not any water entrance
into the LP side impulse line. We need to maintain LP side
without water.
4. All Joints should be tight and there will not be any
leakages.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Difference between 2-Valve Manifolds, 3-Valve Manifolds and 5-Valve Manifolds 3 with diagram
Explain pH, Conductivity.
What are different types of orifice plates? State their uses.
1- Explain about HPM 2- What is the FSC and explain the configuration of FSC 3- explain the complete loop of vibration, how it works (field to control room) 4- What is the use of proxymitter? 5- During job your partner effected with H2S then what you have to do. 6- what type of gland packing uses when valve glind is leaking.
Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com
how to calibrate 0- 150 psi presure gauge by dead weght tester
How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?
In which principles tx ,pressure gauge,Temp gauge,control valve works?
how pressure transmitter work, what is its principal to measure and how its generate signal. for pressure transmitterinstallation which precautions must be taken ??
Why does a pressure gauge installed on reactor, doesn't have any vent line below to release the pressure? Is it any kind of designing mistake or it actually does not require any vent line? And if it does not require any vent line below it then how we are gonna release the pressure built inside the pressure gauge?
what is instrument philosophy
whatis range of marcury filled tempereture gague
What is Span Error
What you mean by multi stage control vavles?
What are advantages and disadvantage of the ac supply load cell?