Answer Posted / s vedpathak
Control valve is used in close loop control system.If it is
hunting , then to troublshoot first put loop for few sec in
manual mode, still if v/v is hunting then it is field
problem i.e v/v or I/P converter problem.
If it is not hunting in manual mode, then the problem can
be either the loop process variable(PV) is hunting or if PV
is ok, either the load/process is varied or loop needs
tuning.
| Is This Answer Correct ? | 57 Yes | 1 No |
Post New Answer View All Answers
what is the input of digital counter during the the calibration time?
what are procedure of sox-nox calibration
What is the use of each wire in three wire RTD
what deference between panel earth and systemearth
What is the purpose of bypass valve across AS valve.
What denotes the 5/8mm in the 3300XL 5/8mm proximitor probe?
Turbidity analyzer working principle ?
How to erection of DCS Panel at site step by step
I installed the smartplant instrument v8, but can not be opened, that always said: "INTools 2007 hardlock no found". So Could you help me how to do for that?
what is use of communication wire in multipare cable(oil and gas field), why this communication wire not used in single pair cable?
WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?
why orfice is not used for main steam flow calculation
Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks
Explain the working of rota meter.
Explain the mechanism behind the turbine meter.