Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

sir,
Two different rating of generator going to connect
parallel, can it set same DROOP or different. Why? Please
explain

Answer Posted / n.v.mani

Higher rated machine should be set at less droop than that
of lower rated machine,for equal load sharing and smooth
operation of system.If both machine ratings are equal,droop
should be equal.

Is This Answer Correct ?    2 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

While performing stability test of differintial cts how to know the voltage and current on both side of the transformer?

3496


1.why are not using acb 33kv ht side? is there any problem 2.what is difference between acb,vcb,sf6 breackers? 3.what is the function of invertor and convertor in ups?

2105


why do you add the load short circuit impedance when considering short circuit amperage. It seems that you should only consider supply. If you need to consider loads and you don't know what loads are to be added , what would be a good sub-transient reactance rating for the loads?

1749


how to control the speed to switched reluctance motor

1888


How the over load setting for HT Motors calculated-provided in Numerical Relay

1740


in ACB breaker requireding 3200Amps. buscoupler getting OFF mode and again it reset and getting normal position give me a required answer?

2299


1) why a dg set shows variation of power factor and load when synchronised with other dgs? 2)Why the load sharing is not become equal in all dgs?. 3)When a dg set will not run on auto start?

1953


what will be project cost for 100 kv transformer connection under oyt scheme.

2876


why the colour of insultor stack , petticoat is brown. Is it has some technical reason.

1972


with help of neat sketch explain principle of TIG welding process

1907


please send me previous year questions of jspl through which i could prepare myself for the test.

1833


How to decide CT & PT ratings for a given transmission line carrying some rated voltage?

2273


How isolater function when installed inelectrical 440V wiring

2164


What is reactive power and where it is used.

1645


why we use copper earthing for neutral while for body GI.

6045