Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to claculate earth strip size for 1500kVA transformer
for neutral and body

Answer Posted / bala.a

you will follow as per State electricity board norms - 50
x 6 mm Cu for Nu and 50 x 6 mm GI FOR body 0r
you will calculate as per short circuit calculation
Formula 0.0054 x root t x I
Where
t =1 second
I = SHORT CIRCUIT CURRENT
example
Fault current- 33kA( assumed )
0.0054 x root 1 x 33000= 178.2 mm
so you will recommended 50 x 4 mm Cu

Is This Answer Correct ?    14 Yes 9 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Draw a SLD of HT distribution EB grid up to users Transformer?

6156


What is meant by analogous system?

1222


What do you mean by ratio correction factor of instrument transformer?

1126


What are the different types of controllers?

1034


How to checked frequency drive output voltages?

1130


I am getting above 60 V as open delta voltage against single phase unit ICT at tertiary delta formed and ICT getting trippped on NDR. ICT tested and found in order. PTs provided on tertiary are tested and in order. what may be the reason?

1813


how test transfomer(3 phase75kva) by megger

2059


What are the significant parts of dc generator?

1079


where rlc series ckt used?

2156


salam&hi, i need to know about how can i calculate an enough current for the new building before i submit it to the suppliers

2035


why the NGR (neutral grounding resistor) always OFF during DG off?

3428


hello if any one have papers vof hpcl or sail, plz send me

1876


induction 3 phase motor terminal connection

2581


plz send me the procedure and syllabus for mseb exam

3806


How to test IR testing & magnetic balance test

1939