how to calculate the size of cable for 100 kva load,?can
somebody tell me with a formula
Answer Posted / virendra
Considering Powe factor 0.8
Kw = KVA*.08
KW = 100*0.8
= 80 KW
w = 1.73 * 415 * Il * 0.8
80000 = 1.73 * 415 * I1 * 0.8
I = 80000/ 1.73*415*0.8
= 139 Amp
You can choose the cable which current carring capacity per
phase is on or above 140 Amp
By considering the future expansion of load the 180 Sq.mm
AYFY cable is ideal.
| Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
in HT service 3ph 4 wire service Y-phase voltage shows zero . whether it is meter fault? or what be the reason ? if y-ph voltage zero ,can current is recorded? reasons for failure?
I Just want do EHS Certified Certification Distance Course From Govt approved,so can any body provide me details.
What are the advantages and disadvantages of closed-loop control system?
If we need 4c× 50mm sq cable but it's not available so we can pull 4c×25mm sq two cables?
I am going to appear RRB Sr. Section Engineer Exam, Electrical. Can you send me previous year questions of RRB Electrical engineer. specially Section Engineer questions. my email id is likerahulworld@gmail.com
how we calculate torque ? how we improve it ?where torque will either motor or generator ?
Do any one know exacatly when the results for NHPC held on 8th march 09 for engineering trainees will be released ?. if so please post it, i'm eager to know it.
how many joint can done in HT line and what is life of the joint
Why space heater is required for each verical bus bar chamber? if one space heater is adequate or not for anti condensation?
when qty of cable being purchased is not sufficient according to the standard,what should the inspector do to ensure its quality according to the standard?
i am going to give the JSEB,RANCHI exam for power plant,so i need some samples of papers related to that,so please send me these papers by my mail id.
234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,
Sir, I m 3rd year student 4m DCE and want to do internship in siemens or l&t or any other mnc related to electrical engineering. please tell me the procedure 4 same and oblige me
where can i get vijaya electricals limited in hyderabad interview auestions can u give me the website address plz
If a current -8+6sin6t is flowing three ammeter, one is a centre zero PMMC meter, one is true rms meter and one is moving iron meter. What are the reading of these three meter respectively?