how to calculate the size of cable for 100 kva load,?can
somebody tell me with a formula
Answer Posted / virendra
Considering Powe factor 0.8
Kw = KVA*.08
KW = 100*0.8
= 80 KW
w = 1.73 * 415 * Il * 0.8
80000 = 1.73 * 415 * I1 * 0.8
I = 80000/ 1.73*415*0.8
= 139 Amp
You can choose the cable which current carring capacity per
phase is on or above 140 Amp
By considering the future expansion of load the 180 Sq.mm
AYFY cable is ideal.
Is This Answer Correct ? | 18 Yes | 2 No |
Post New Answer View All Answers
How isolater function when installed inelectrical 440V wiring
In the Variable Voltage Variable Frequency Drive, how the Voltage and Frequency varied ? Is it varied in the Inverter part of the Drive ? Please give us supporting document if any.
What are the different losses In a de mac1une'! t.xplam
how freewheeling diode improves the powerfactor
How to reduce the static electricity producing in solvent room? By P.D.Patil BioCon
What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.
what is the difference b/w absolute encoder and incremental encoder?
while starting a liquid starter ,is there any volage drop on water/soda on tank.can we touch the tank on starting?
what's the requirement of Dy11d0 connection of 3 phase transformer?what's use of it?
i am in need of AC SYNCHRONUS MOTOR 30KW. ANY ONE KNOWS THE MANUFACTURER OF SAME. ALSO MOSFET AC CONVERTER 20KVA CONT.OUTPUT.
how will reduce the voltage. if 12volt/250ma transformer toreduce 6 volt
i have interview in Pepsi company what type of question will ask please send the question and answeer
and gate circuit diagram,amplifier circuit diagram
"TRANSFORMER MODELING AND ANALYSIS" MEANS WHAT AND WHICH TOPICS U READ IN THIS
direction of tarbine& genrator