How can you calculate in detail the VA burden of current
transformer used for Restricted earth fault protection?
Please understand that the CT required here is Class PX or
X. Also please show the calculations for knee point vtg,
stabilizing resistor, magnetising current.
Answer Posted / william lobo
Knee Point voltage is nothing but a point at which the CT
saturates. Thats why its always better to design the CTs
which can operate without saturation even at a voltage
appears in the CT during fault condition. Pls find below
the following formula for calculating the Knee point
voltage.
Vk=2If(Rct+2Rl).
where, If is the current refected to the CT secondary
during fault condition,
Rct is the resistance of the CT which can be adopted by
means of a thumb rule considering the CT ratio,
Rl is the lead resistance i.e. sum of the resistance of the
wire connected between the relay & CT and Impedance offered
by the internal circuitary of the relay
For PS class CT's designed considering the above,burden is
not applicable.
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
single phase power supply give to separate one steel coup with water, what reaction create
what is the differance between HT motors And LT MOTORS.
how to get electrical supervisor competency certificate in gujarat. i did 3 year diploma in electrical
What is safety of Ht panel
A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?
What is the end effect of linear induction motor ??
how many Classification of fire extinguisher
What is ferro-resonance in electrical system? Why it occurs and what are measures to prevent it?
1600kva capacity Transformers how the bucholz relay,Oil temperature,winding,surge relay relays setting are to be done
what is the function of impulse relay
how to find the capacitance value of the motor while running??
What is the physical significant of power factor?
How does the phase sequence controller works, how it identifies the phases? confirm working principle
How to detect voltage vector shifting in interconnection protection.
Define norton equivalent circuit?