Answer Posted / sangeetha.np
The percentage represents the amount of normal rated
primary voltage which must be applied to the transformer to
produce full rated load current when the secondary winding
is short circuited. The maximum short circuit current that
can be obtained from the output of the transformer is
limited by the impedance of the transformer and is
determined by the multiplying the reciprocal of the
impedance timed the full load current . Thus, if a
transformer has 5% impedance, the reciprocal of .05 is 20
and maximum short circuit current is 20 times the full load
current.
| Is This Answer Correct ? | 4 Yes | 2 No |
Post New Answer View All Answers
We have given to 3phase supply to ups system & how can coming netural
what is the IS foe lightning arrester?
Why the standard of ambient teperature mentioned as 40 degree celcius in machines.
What is the complete procedure of erection of electrical panel in industry
c++ write a program to use a fuction call "max"which accepts an intger arrey of size5.as an arrument and return the larger and smallest of the arrey to main without changing. the original changing of the original position of the element of the arrey.
which phase is preferred for connecting 1 phase vt used for synchronizing OHL? WHY?
How to Calculate The sag of OPGW in Transmission Line???
what happens if earth of 33kv cable is not connected to earthing pits? please send this query's answer to ngrm.sudha249@gmail.com
how to calculte capacitor range for single phase induction motors??pls tel
what is the condition for YnD11
what are the range of memory address in plc for L&T lx7 4A
from which formula we select a capacitor rating?
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
why on delay timer used for fully automatic star delta starter?
wish of these transformer uses oil?