Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to calculate earth flat size for 250 Kva DG and
transformer?

Answer Posted / samson

Neutral will come in to picture whenever u start ur DG (
and not paralleing with a Grid as it will create a
circulating current), so worst thing that can happen is L.G
fault on a phase of generator or inside the winding , so
max current that can go is dg rating/ phase volatge ( use
formula above) so ur neutral should be capable of that
much curent ,( neglecting any contact resistance in ideal
case)

the switching of neutral is done through contactor.

use this to size strip
the I = K* A/ sqrt of time ( some of IS standered give u k
for bare conductor) Dg manufacturer will size support for
S.C forces

get k for alumi. or copper u can size to next standered
sizes available 20 x 6, 40 x5 n all

Is This Answer Correct ?    4 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to design pavement quality concrete by using C.R.C.P Method

1746


What are the basic components of the feedback control system?

1053


Is it advantages of having star-delta vfd than normal star vfd , if yes why?

2258


WHAT IS THE SIGNIFICANCE OF VECTOR GROUPS IN TRANSFORMER? WHAT WILL BE EFFECT WHEN PHASE DISPLACEMENT CHANGES IN TRANSFORMER?WHAT IS THE NEED TO BE PHASE SHIFT CHANGE BETWEEN THE PRIMARY AND SECONDARY WINDING

1788


What is the power requirement of tamil nadu for one month?

2021


Can anyone please provide me details of MCCB/Contactor/SFU rating calculations for a motor feeder..for example 50 kw.. not from type-2 cordination chart. i want manual calculations..

2588


tell me some type of questions throught which i can prepare for exam and do my best

2017


what is the use of Auto re-closer?

2145


WHY MOSTLY Rph IS USED FOR CONTROL CIRCUITS AUX. SUPPLY ?

2502


how can i use REF and diffrencial relay both in 1 CT core for transformer protection?

1869


in indoor type circuit breakers why only the corner breaker trips specially during cold season. What is the reason.

1879


What is difference between SMC supportg and Glass Fibre Reinforced Plastic Support.

2341


Why synchorised generators are used for the production of electricity?

1186


which protection used in power plant?

1958


Plz tell me how we can find that particular company has vacancy or not

2272