what is the size of ht cable of 33kv ht line and
transformers ratings are 2.5mva and 5.5mva.please send
formula also.
Answer Posted / eng. d
first, how will you install it?
underground direct buried, inside trenchs or above ground
any ways, the way to calculate will be done by the cable
vendor but you can do rough estimation
for 2.5 MVA transformer
= 2.5MVA/(1.73*33KV)=43 A
then cable shall be derated and much more than transformer
then we can say we select 60A cable rating
then we go to cable vendor catalog
try to see this
http://www.doncastercables.com/cableCalculator.asp
thank you
| Is This Answer Correct ? | 10 Yes | 1 No |
Post New Answer View All Answers
how to select battery for 15 KVA UPS with formula
we specify current in case of feeder but in case of distributor voltage, why?
please send me the L&T Emb. sys. placement papers and entire details of pattren
What are the special cables required for explosion proof wiring?
What is voltage ratio of a transformer?
how to avoid Saturation in C.T?
what is diff. between earthing grid,earthing mess, earting grid?
Is there chopping current in resistive circuit
What are the advantage of free wheeling diode in a full wave rectifier?
sir, what is the importance of Fault MVA. how to calculate fault mva of 33kv substation connected by 6.5 km line(single circuit with equal spacing) with 110/11kv transformer in 110kv susbstation.the fault mva on 11 kv bus in 110kv susbstation is 208mva.
how can we find thae value of capacitor for single phase motor. what is difference between starting capacitor and running capacitor.
how the B-H loop obtain under the static condition
What is meant by positive and negative feedback?
What is the dependency of stiffness on load angle??
Can anybody tell abt concrete encased earthing or grounding?