We have 2 Nos. Transformer with the capacity of 2000KVA and
1250 KVA and currently using only one 2000KVA T/R during
operational hours while non- operational hous 1250 KVA T/R
also used to reduce T & D losses. Similarly, 2 capacitor
bank of 500KVAR and 300 KVAR also installed to balance
reactive power. Now problem is around 1000 KW load PF is
not maintaning 0.99 as 350 KVAR capacitor is in healty
condtion. Now the PF is maintain 0.95 to 0.96.
Answer Posted / arvind
You please check out the location of the capacitor banks
means whether it is away from the load or not if it is away
from tha load then power losses will be there and affects
the power factor.
secondly, if the load (1000kw) is variable means motor,
then it is difficult to get power factor 0.99.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
What is the effect on 3phase induction motor if current setting knob of DOL kept at minimum current?
Haw to check conductivity of budbar
EXPLAIN THE TRANSFORMER MAINTENANCE?
what is the safty of poly phase tranformer?
what is the formula to calculate voltage drop/loss on 66KV Transmission Line?
hello!my name is sheikh iam preparing for indian engineering servieces,please send me the old question papers..to sheikhshaazforjobs@gmail.com
What is warm / cold start of HT motors. How many warm start & cold start are possible in a day?
Explain what is electric traction?
what is KSR type transmission tower? What is LSR type transmission tower?
Load break swicth maintenance procedure.
What is pole of the system?
what is transient voltage?
what is the basic construction diffrance between servo motor ans sqiralcage induction motor
what is the ground fault relay,which purpose it will be use,clearly tell me plz
why wire sizes are 3/29 or 7/29 and why not wire sizes are 2/29 or 6/29?