from 33kv to 440v 2mva transformer how much full load
current will be at ht side and lt side and which range of
ctpt will be used?
Answer Posted / bala.a
35 A on HT Side 2625 A on LT Side nd requiired CT on HT
side will be 50A and LT side 3200A (because the standard
breaker rating is 3200 A )
| Is This Answer Correct ? | 7 Yes | 4 No |