How can we calculate ngr resistance for a generator and
Transformer ?
What type of transformer requires ngr ?
Answer Posted / pavan
The value of the NGR to be inserted in the cicuit can be
calculated by the simple formula
R = V / (√3 * I)
Where V is the System Line voltage in Volts
I is the value of the fault current to be limited
In general practice the fault current is limited to the
full load rating of the largest equipment available in the
system.
| Is This Answer Correct ? | 6 Yes | 5 No |
Post New Answer View All Answers
I want formula to calculate cable size as per load given in length & amp. I searched many sites but didn't right answer. Please reply me asap.
How can eliminate noise problem inside temperature controller temp. variation due to contactor chattering problem.
Why do we pefer VCB over OCB?What are the advantages of VCB over OCB?
Is neutral transformer can be called as control transformer?
Why power factor should not be in leading (capacitive) mode of any load.
PLZ EXPLAIN THE INTERLOCKING AND CONTROLLING OF CONTACTORS????HOW CAN I DO THAT?
when the Transmission and Distribution network where is the "feeder" lines are located? and why should be used in T&D network.....
What are the application of filter?
is it possible to start a motor in felid connected to a remote mcc
What is Icu and Ics and what is difference b/w them. please tell me how to calculate a size of a copper bar for a system or a breaker... reply on... king.arish@gmail.com would be waiting for a logical answer.
For a 6.6kV Motor it is recommended to do megger test with 500 V d.c and not more than 5kV d.c but the Hi voltage withstand test should be performed by 12kV AC. Why the dc voltage test should be limited but AC voltage withstand test could be with such a high voltage?
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?
I am having a 42KW 3 phase electrical heating furnace, heating element is 80/20 nichrome material, my connections is made in such a way that 2 star connection compromising 2 coils per phase so totally 12 coils, shall if i use it unbalanced star condition (instead of 2 group of 3 phase or 1 group of 3 phase, connecting 4 phases of 5 phases) what will be the consequences and is it acceptable?
Dear all, how we select the cable size according to current with or without including different correction factor , is there any direct method for sizing of cable...
1.what is mean by 8/20 micro sec waveshape