Why tripping not occur when the transmission lines (11KV &
above) breaks? Doesn't
we provide earthfault protection for it?
Answer Posted / k.prakashchandra
All the tr lines should be provided with EF protection.11
and 33 KV lines are provided with 2 OC and 1 EF relays or 3
OCR and 1 EFR.The unbalanced current passes through the EFR
which is usually set at 20% of OCR setting.The EFR is
connected between star points of CT's and relays. For
higher voltages distance relays are provided with OCR and
EFR as back up protection.If the line breaks i.e.a
conductor opens out without touching earth .The distance
relay does not act as there is no heavy current.The EFR
will trip only if the unbalanced current exceeds the set
value .Hence there will not be any tripping if the line is
not loaded sufficiently. OCR=over current relay, EFR =earth
fault relay
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Is it a better option to procure screw type air compressor rather than reciprocating air compressor?If so, what is the reason?How should we select an air compressor(100 CFM)? Please mention the important parameters of air compressor.
how power is generated,and transmitted to our home..pls explain briefly in simple words.
What conditions are required for transformer to operate at low frequencies ?
what transformer we used normally and upto which kva?
how to increase or decrease speed in DC shunt motor by DC convertor
why booster transformer is used in sumpners test conducted on transformer????
How the over load setting for HT Motors calculated-provided in Numerical Relay
what is the voltage regulation for unity and zero power factor?
which of the following elements is not present in stainless steel
Battery is a voltage source? give one example of current source and why?
how to calculate distance between busbar supporters for LT panel, what are the factors influencing in this design
what do w do when the output of generator is fluctuating?
why sometime we get electrical shock while touching the ballon of dish tv connection ? which we should not get.
in my industry we are using 3 step up transformers for induction heaters..i.e 415/580v and other are 11/440v.in power consumption does a step trnsformer makes any difference compared to step up?? plz explain
How do we find the rating of a transformer, if it got burnt badly.