Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Why tripping not occur when the transmission lines (11KV &
above) breaks? Doesn't
we provide earthfault protection for it?

Answer Posted / k.prakashchandra

All the tr lines should be provided with EF protection.11
and 33 KV lines are provided with 2 OC and 1 EF relays or 3
OCR and 1 EFR.The unbalanced current passes through the EFR
which is usually set at 20% of OCR setting.The EFR is
connected between star points of CT's and relays. For
higher voltages distance relays are provided with OCR and
EFR as back up protection.If the line breaks i.e.a
conductor opens out without touching earth .The distance
relay does not act as there is no heavy current.The EFR
will trip only if the unbalanced current exceeds the set
value .Hence there will not be any tripping if the line is
not loaded sufficiently. OCR=over current relay, EFR =earth
fault relay

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

i need of the bhel question papers along with answers and also give some website names for the downloading question (electrical and electronics engg question)please help me....

1921


What is difference between start imitation and start interlock for 3 phase motor protection ?

2253


A logic circuit that provides a HIGH output if one input or the other input, but not both, is HIGH, is a(n)?

1244


what is the importance of Partial Dischage test for Electrical Equipments

1934


If 100 KAV USP dedicated earth got disconnect / Cut. What will happen at load.

1971


what do you mean by plant earthing system.

2070


What is turn ratio of a transformer?

1240


how can calculate resistance box for 15 kw, 6 pole, RV-230, RA-42 motor

3339


Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.

2359


What happen in ups if phase reverse?

2295


What are the two basic types of transformers?

1175


TRANSFORMERS WITH DC SUPPLY

2086


How eddy current generation support the idea of train braking?

2003


ANY ONE TELL ME ABOUT generator synchronization panel panel to synchronise 3 gen of 250kva both automatic and manual. 2 gen output vol 415 3ph, 1 gen output vol 400 3ph SEND THE DETAILS DIAGRAM ON THIS EMAIL ADDRESS ayazleo@hotmail.com as soon as possilble best ragrds electrical engineer ayaz mahmood SAUDI TECH

4164


What do you mean by a current transformer?

1094