how much load 15kva dg set can bear.with full explination
and how to calculate?
Answer Posted / amit chaudhary
The full load of 15 Kva DG set will be 12 KW on 0.8 power
factor. if the DG set is 3 phase(415 v) then per phase
current will be I = 15000/(1.732X 415)= 20.86Amp/PHASE
| Is This Answer Correct ? | 28 Yes | 8 No |
Post New Answer View All Answers
Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?
what is the function of impulse relay
Bimetal strip used in overload relay what is that,which types of material used for that & percentage.
Inductor and capacitor........power in one phase and ...... in it another phase.
The 3 phase Delta connection RB=440V, BY=350V,.......* is Line to Line voltage RY= ? And Formula....?
What must be the minimum distance maintained between 2 Generators as per International standards?
What is meant by stator? What is meant by rotor?
i installed 100kva ups. what KVA genset they should provid in input side? plz any update formula or ans with reason.
The principle of switching circuits for different types of batteries in application of storage systems
What is a system?
What are the different types of transformers?
give some advantages and disadvantages of combiniing the session, presentation, and application layer in the osi model into one single application layer in the internet model
how to store the thunder power?
take 100kva DTR( delta/wye ), what ll happen if we connect 11kv to LT side instead of connecting to HT side? will the DTR behave as a step up transformer or something else????
What is Meter MF if External CT Ratio is 150/1 , PT Ratio is 132/110 Meter CT Ratio is 200/1 & Meter PT Ratio is 110/1