what is the role of impedance in transformer?based on
secondary f.l.current(139 amps) and impedance(4.07) of
415/415v of 100 kva transformer. what is the primary
current?
Answer Posted / ma.amulraaj,b.e. mba.,
It is %impedance Voltage.In Transformer,%impedance Voltage plays significant role .Here 100KVA,11KV /415 V.
Full load current Sec .current= VA / 1.732x V (Sec.Voltage)
=(100x 1000 )/(1.732x415 ) =139 Amps, ok
Full load current Primary .current= VA / 1.732x V (Primary
Voltage)
=(100 x 1000)/(1.732 x 11000)
=5.25 Amps
Here ,the full load secondary current is 139 Amps,the rated secondary voltage is 415 V,we can do Short circuit test by applying secondary voltage 415 V,we cannot get the full load secondary current,due to impedance of Transformer.Then we have to raise the secondary voltage gradually, at particular voltage it delivered the full load secondary current,note down the voltage say 440V.From that voltage we have to find out % impedance.440 /11000 = 4% %Z=4.0 %.As this case %Z=4.07,ie. it is (4.07 x11000)/100 =447.7 V.It means This transformer may delivered a full load current at 447V.
This % Impedance may vary from Transformer to Transformer.
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
in shunt clippers why a resistor is used in sereis with the input
what are the standard IR values should be of R-E, Y-E, B-E, R-Y, Y-B, B-R of VCB in closed condition and in open condition for 500KVA & 1000KVA transformers. and what is the acceptable range when tested by 5000V megger.
1.how many earth pits are required for 1000 k.w plant include substion , transformer ? 2. how many earth pits are required for 500kva generator.what is formula to calcute?
Explain about 3 phase motor fault current calculation with examples?
Hello everyone, somebody knows what is a "surplice power" ? The hole phrase is: "This rating is appropriate for a generator set paralleled with an infinite bus e.g. a national electrical supply network or grid where the generator set is run at 100% load, 24 hours a day, 365 days a year and any surplice power is exported into the grid" Thanks in advance.
how to calculate power consumption in slip ring motor at different step
What is effect of harmonic current (Draw by VFD) on power system/ electrical Equipments ?
Terminal blocks is used for segregate the connections... There is any principle for terminal block..?
explain single phase series motor
how to find the multiplication factor for digital energy meter and analog energy meter
What descriptive information does the NEC require to be marked on all conductors?
when it is possible kvrah lead & fundamental kwh be equal in electonic trivector meters (3 ph)
why use phase displacement in transformer.and effect of phase displacement on transformer
Why have to use copper cable for local isolator to motor ?
How wire size can define in electrical wiring? What is the ratio?