Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is the role of impedance in transformer?based on
secondary f.l.current(139 amps) and impedance(4.07) of
415/415v of 100 kva transformer. what is the primary
current?

Answer Posted / ma.amulraaj,b.e. mba.,

It is %impedance Voltage.In Transformer,%impedance Voltage plays significant role .Here 100KVA,11KV /415 V.


Full load current Sec .current= VA / 1.732x V (Sec.Voltage)


=(100x 1000 )/(1.732x415 ) =139 Amps, ok


Full load current Primary .current= VA / 1.732x V (Primary
Voltage)


=(100 x 1000)/(1.732 x 11000)
=5.25 Amps

Here ,the full load secondary current is 139 Amps,the rated secondary voltage is 415 V,we can do Short circuit test by applying secondary voltage 415 V,we cannot get the full load secondary current,due to impedance of Transformer.Then we have to raise the secondary voltage gradually, at particular voltage it delivered the full load secondary current,note down the voltage say 440V.From that voltage we have to find out % impedance.440 /11000 = 4% %Z=4.0 %.As this case %Z=4.07,ie. it is (4.07 x11000)/100 =447.7 V.It means This transformer may delivered a full load current at 447V.


This % Impedance may vary from Transformer to Transformer.

Is This Answer Correct ?    3 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

dg earth connect only in the amf panel or not why

2082


Do closed loops systems require manual input?

1196


What is speed mode?

1698


how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take

2123


how withstand of hi-pot test outputs of transformer wire 2.5mm

1962


how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar

2010


how to interlock 3 nos MCCBs using under voltage coil. please provide me circuit diagram?

2601


what is breathing?

1811


can I improve the furnace power factor (10 mva transformer) by adding a capacitor bank before the transformer.Does system power factor vary a lot with the furnace PF?

2038


What are the different power system losses and how can it be eliminated?

2046


various transmission tower like .,D tower ,K.C.O tower ,C.C.O tower,K.C.R tower ,C.C.R tower ,H.C.O tower in different tons.

3294


Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?

1819


Why synchronous motor is used in power factor improvement,dc series in lift

1654


how to calculation increase power factor for single phase

2291


How to calculate multiplication factor in kva example 500kva ans pls ?

1949