what is the role of impedance in transformer?based on
secondary f.l.current(139 amps) and impedance(4.07) of
415/415v of 100 kva transformer. what is the primary
current?
Answer Posted / ma.amulraaj,b.e. mba.,
It is %impedance Voltage.In Transformer,%impedance Voltage plays significant role .Here 100KVA,11KV /415 V.
Full load current Sec .current= VA / 1.732x V (Sec.Voltage)
=(100x 1000 )/(1.732x415 ) =139 Amps, ok
Full load current Primary .current= VA / 1.732x V (Primary
Voltage)
=(100 x 1000)/(1.732 x 11000)
=5.25 Amps
Here ,the full load secondary current is 139 Amps,the rated secondary voltage is 415 V,we can do Short circuit test by applying secondary voltage 415 V,we cannot get the full load secondary current,due to impedance of Transformer.Then we have to raise the secondary voltage gradually, at particular voltage it delivered the full load secondary current,note down the voltage say 440V.From that voltage we have to find out % impedance.440 /11000 = 4% %Z=4.0 %.As this case %Z=4.07,ie. it is (4.07 x11000)/100 =447.7 V.It means This transformer may delivered a full load current at 447V.
This % Impedance may vary from Transformer to Transformer.
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
dg earth connect only in the amf panel or not why
Do closed loops systems require manual input?
What is speed mode?
how to calculate the cable current ratingand and how much of distance the rating will be ok will the distance is incresed what the action we take
how withstand of hi-pot test outputs of transformer wire 2.5mm
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
how to interlock 3 nos MCCBs using under voltage coil. please provide me circuit diagram?
what is breathing?
can I improve the furnace power factor (10 mva transformer) by adding a capacitor bank before the transformer.Does system power factor vary a lot with the furnace PF?
What are the different power system losses and how can it be eliminated?
various transmission tower like .,D tower ,K.C.O tower ,C.C.O tower,K.C.R tower ,C.C.R tower ,H.C.O tower in different tons.
Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?
Why synchronous motor is used in power factor improvement,dc series in lift
how to calculation increase power factor for single phase
How to calculate multiplication factor in kva example 500kva ans pls ?