How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva
oil type transformer system?
plz provide step by step calculation
Answer Posted / madhu mohan
First calculate the current of primary side(HT) and derate the cable by atleast 0.7.
Eg:1500*1000/(1.732*11000)=78.73A
Current I after Derating =78.73/.7 =112A (0.7 if laid on the trays or value will vary if buried in the ground).
Cable equivalent to rating has to be selected.
Now Short circuit withstand capacity (sq. of I X t in sec) has to be checked from the cable catalogue.This value of cable should be higher then SC withstand capacity of the ground usually it is 50KA.it less go for next size and finalise.
| Is This Answer Correct ? | 32 Yes | 24 No |
Post New Answer View All Answers
What are the disadvantages of hydropower?
IF TVM OF TRANSFORMER SHOWS POWER FACTOR ON 33 KV SIDE AS 0.97 LAGGING AND ON 132 KV SIDE IS 0.75 LEADING.IS THIS CORRECT.WHERE IS PROBLEM.
why Lightening Arrester Probe sharp at Top of telecom tower.
Why auxiliary transformers are not connected in parallel in primary stations?
why ahould you show client/engineer activities clearly on the project plan
What is the basis for selecting Vk/2 or Vk/4 for REF and Differential protection of Transformer and What is the significance of magnetising current
what is inverter and converter
Is it true that in the 3 phase transformer, the limbs of the core are at 45 dgrees to each other. if true, why?
electromechanical relay type identification example : type=tjmh t-stants for j- m- h-
design a 3 bit synchronous and asynchronous counter using T- flipflop
Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?
Explain Creepage Distance of Insulator
Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com
If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.
can u tell me the promotion from oiller to enginer