Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How to calculate HT XLPE CABLE for 11 kv / 433 v , 1500 kva
oil type transformer system?
plz provide step by step calculation

Answer Posted / madhu mohan

First calculate the current of primary side(HT) and derate the cable by atleast 0.7.
Eg:1500*1000/(1.732*11000)=78.73A
Current I after Derating =78.73/.7 =112A (0.7 if laid on the trays or value will vary if buried in the ground).
Cable equivalent to rating has to be selected.
Now Short circuit withstand capacity (sq. of I X t in sec) has to be checked from the cable catalogue.This value of cable should be higher then SC withstand capacity of the ground usually it is 50KA.it less go for next size and finalise.

Is This Answer Correct ?    32 Yes 24 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the disadvantages of hydropower?

1304


IF TVM OF TRANSFORMER SHOWS POWER FACTOR ON 33 KV SIDE AS 0.97 LAGGING AND ON 132 KV SIDE IS 0.75 LEADING.IS THIS CORRECT.WHERE IS PROBLEM.

2419


why Lightening Arrester Probe sharp at Top of telecom tower.

1606


Why auxiliary transformers are not connected in parallel in primary stations?

1463


why ahould you show client/engineer activities clearly on the project plan

2830


What is the basis for selecting Vk/2 or Vk/4 for REF and Differential protection of Transformer and What is the significance of magnetising current

2450


what is inverter and converter

1974


Is it true that in the 3 phase transformer, the limbs of the core are at 45 dgrees to each other. if true, why?

2125


electromechanical relay type identification example : type=tjmh t-stants for j- m- h-

2493


design a 3 bit synchronous and asynchronous counter using T- flipflop

2062


Why 30kw 40 hp 4 pole 3ph induction motor over heated?any steps on reduction in heat?

1730


Explain Creepage Distance of Insulator

2258


Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com

1980


If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.

1489


can u tell me the promotion from oiller to enginer

1984