Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.

Answer Posted / virendra joshi

Dear friends,


Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA

you can go with 600 KVA D.G set .

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

whate is the meaning of balance/unbalance,in stabilizers type

2186


EXPLAIN USE OF ROCKING ARRANGEMENT IN ELECTRIC HEATING?

1976


what are the condition that makes hooter blow?

2510


what is the usage of microcontroller in the panel board?

2138


how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar

2076


What is 100% protection of generator? Why 100% is not used but 95% is generally used?

1091


what is the major difference between LIBBP & HIBBP.. which one is most preferable..

3067


what is the significance of tan&delta and how it performed in power transformer

1978


What is the end effect of linear induction motor ??

2074


What is mean by hot and cold loop testing? What is the difference between them?

1174


Main advantage of auto transformer over two windings transformer is that A it needs no cooling B it uses only one winding C core losses are reduced D it has simple construction

2984


Please send 110 kv sb station full single line drawing(sld)

2522


What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.

1711


WHY SEPARATELY EXCITED MACHINE NEEDS EXCITATION BY DC SUPPLY WHY NOT BY AC

1945


battery capacity use of made?

2597