If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / virendra joshi
Dear friends,
Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA
you can go with 600 KVA D.G set .
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
whate is the meaning of balance/unbalance,in stabilizers type
EXPLAIN USE OF ROCKING ARRANGEMENT IN ELECTRIC HEATING?
what are the condition that makes hooter blow?
what is the usage of microcontroller in the panel board?
how to select size of hardware for linking aluminium busbar is it depend on area of busbar or current flowing through bus bar
What is 100% protection of generator? Why 100% is not used but 95% is generally used?
what is the major difference between LIBBP & HIBBP.. which one is most preferable..
what is the significance of tan&delta and how it performed in power transformer
What is the end effect of linear induction motor ??
What is mean by hot and cold loop testing? What is the difference between them?
Main advantage of auto transformer over two windings transformer is that A it needs no cooling B it uses only one winding C core losses are reduced D it has simple construction
Please send 110 kv sb station full single line drawing(sld)
What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.
WHY SEPARATELY EXCITED MACHINE NEEDS EXCITATION BY DC SUPPLY WHY NOT BY AC
battery capacity use of made?