If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / virendra joshi
Dear friends,
Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA
you can go with 600 KVA D.G set .
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Main advantage of auto transformer over two windings transformer is that A it needs no cooling B it uses only one winding C core losses are reduced D it has simple construction
a)In a 3-phase 4-wire circuit, a circuit breaker is selected to protect the circuit whose highest fault level is 6.6 MVA. Determine the required minimum breaking capacity in kA. (Note: Covert 3-phase power in terms of kA to find answer.) b)Using the below, determine the required minimum making capacity in kA as a “peak value”. Rate breaking capacity (Icn) ka: Icn<= 1.5 Factor = 1.41 1.5
how we explain parallel paths armature winding?
what is the difference between skin effect
What are the basic component of a cro?
Is it true online ups having bypass mode if it is true then why we called ups because it is interrupting power when goes in bypass mode
What is the difference between amorphous core transformer and CRGO core transformer?.
what is the Connected Load (kW) or Contract Demand (kVA)of mahindra nasik plant??
Testing report of Earthing of 3.15 MVa PTR.
how does the terminal voltage of transmission lines increase when a capacitor is connected???? This happens not only in transmission lines but also in all circuits. How??? When a capacitor is connected in a transmission line, capacitor also takes energy from the same supply. But how is it able to increase the terminal voltage??? Practically What sequence of events happen during increase in voltage???
why you don not show protection and type of isolation in key single line diagram?
Why do we perform an open-circuit test and short-circuit test on the transformer?
Make a list observation on Transformer?
why r we using shell transformer for low voltage
what is mppt (maximum power point tracking ) and how they used in solar power generation ??? what are the main components used in mppt?????