If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / virendra joshi
Dear friends,
Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA
you can go with 600 KVA D.G set .
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Define newton's law of viscosity.
what is the control circuit for operating the clean room air shower
HOW TO CALCULATE THE VT SIZING?
Difference between rating factor of cable and derating factor of cable?
What types of question are done for diploma students in aptitude test
what is R Core Transformer. how it differs from normal transformers. dont search in net and post the answer.
how can i determine the gear ratio for a rack and pinion system if an electronic gate operated by an electric motor is to travel a distance of 5meters in 15 seconds.
What are n circles?
can u please mail me the syllabus for GET exam for damodar valley corporation?
plz explain the auot-reclosing circuit in electrical engineeing
What are the types of windings according to the construction?
what is the function of statics switch in ups and tell me parts
Different STANDARDS (BS, IS, IEC etc) gives different informations on CT specification. How they correspons w r t each other (i.e I mean to say BS provides "knee point voltage" but IS does not, then how can i select CT)
What is the method of estamating of cable, CB,MCB ?
ACCORDING TO IEC WHAT SHOULD BE THE MINIMUM HEIGHT OF G.I. STRUCTURE OF CT, PT, ISOLATOR, LA?