If connected load of Asphalt plant is 375Kw. What suitable
KVA DG set is required. What is calculation formula. what
extra load have to consider. in what efficiency it will
work.
Answer Posted / virendra joshi
Dear friends,
Total Connected Load = 375 KW
KVA required @0.8 PF = 375 /0.8 = 468
Taking a 0.8 as a Demand Factor = 468 *0.8=375 KVA
Considering running of D.G set on 80% load = 3750.8=468 KVA
Considering 20% load for future expansion = 468 + 20%(93KVA)
Total KVA of D.G set = 561 KVA
you can go with 600 KVA D.G set .
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is block diagram?
In radial network the source is fed from 1 end both ends at central
The power supplied to a 33microF capacitor from a 120V, 60Hz source will be
Post possible questions for Power Factor Panel FAT / SAT
Do any one know exacatly when the results for NHPC held on 8th march 09 for engineering trainees will be released ?. if so please post it, i'm eager to know it.
Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?
how to introduce yourself
How to calculate no of EARTH PIT? Describe the formula as per IS standard?
in parallel operation of power transformer why the distance between power transformer and capacitor bank feeder is necessary to know
What are the difference between normal application Transformer and Solar application Transformer?
How we select the vector group of 3phase power transformer?
what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV
what is meant by the phrase 'static load' in case of shorting in a generator excitation system?
it is possible to measurement of tension of slipring induction motor(SRIM)carbon brushes, any maesuring instruments are available in the markets.
how will reduce the voltage. if 12volt/250ma transformer toreduce 6 volt