how to estimate the breaker capacity of breaker,please give
the one example( 6.6 kv breaker,800a)?????
Answer Posted / raghavendran.r
Step1: Calculate the system MVA.I have calculated that as 1.732*6600*800 = 9.144MVA. I have taken it as 10 MVA for easy calculations further.From the system MVA find out the Fault MVA value using the per unit impedance.i.e
Fault MVA = System MVA /P.u.Impedance.I am taking iot as .1
Hence we arrive at the Fault MVA.From this condition we get to know the Short circuit current as Isc = Fault MVA/Sys Voltage(6.6kV).
Usually, for a 6.6 kV system, the short circuit withstand rating is 40kA for 1 second.The Momentary current or making current is 2.55 times the Max. short circuit current.hHence we arrive at 100kA(Peak)
| Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
for 4 MVA , 33K.V/6.6K.V transformer. secondary side the connected load is 3000H.P. What is the rating of capacitor bank to be insttaled.
If oil and air can withstand a high MeV when used as an insulator in a transformer, what are the values of how high for each material?
how to design step down 12 V, 1mA small transformer from 220 V AC? Because according to VI relation and power transfer it results bulky...
what is the voltage between earth & neutral in 3 phase electrical connection.
Can you explain about TEE protection scheme?
Stator of 3-phase IM has 3 slots per pole per phase. If supply frequency is 50 Hz, calculate the speed of rotating stator flux A 1000 rpm B 500 rpm C 1500 rpm D 1440 rpm
draw the restricted earth fault protection circuit install on power transformer and identify its parameters and draw C/C curve of it
How the setting of the vector surge relay shall be calculated when the relay is to be used for Grid islanding application?
Dears we deal in Chemical are Plate earthing. Kindly call if any requirement and questions. Tech Earth Solutions Mohit Verma 8791071007
Why back emf used for a dc motor? Highlight its significance.
What would be the size of wire used for 2 Ton of window A.C?
In the ACB breaker capacity is 2000Amp but this each phase taken 1250 But total beldibg load is 600amp or 700amp watt is the problem
what happens in the short circuited secondary transformer,if the resistance of the short circuit is increased gradually?
What will be result if we connect LT votage to the terminal of HT motor?
control & auxilary circuits used for circuir breakers