Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to estimate the breaker capacity of breaker,please give
the one example( 6.6 kv breaker,800a)?????

Answer Posted / raghavendran.r

Step1: Calculate the system MVA.I have calculated that as 1.732*6600*800 = 9.144MVA. I have taken it as 10 MVA for easy calculations further.From the system MVA find out the Fault MVA value using the per unit impedance.i.e

Fault MVA = System MVA /P.u.Impedance.I am taking iot as .1
Hence we arrive at the Fault MVA.From this condition we get to know the Short circuit current as Isc = Fault MVA/Sys Voltage(6.6kV).

Usually, for a 6.6 kV system, the short circuit withstand rating is 40kA for 1 second.The Momentary current or making current is 2.55 times the Max. short circuit current.hHence we arrive at 100kA(Peak)

Is This Answer Correct ?    2 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the meaning of utility ground and clean ground? How the distribution panel is grounded?

2596


HOW TO CALCULATE THE REGULATION OF 100 AND 25 KVA TRANSFORMER

2070


What are stable systems?

1154


What is the end effect of linear induction motor ??

2075


Electromagnetic torque developed by the motor is compared to shaft torque. A less B same C depends on motor design D more

2095


would the same effect be achieved by reversing the connection to one winding of the induction motor 3-phase?

1869


How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer

1804


We have 750KVA DG set, we want to introduce REF relay with 1250/1A,CL PS,Current transformers.The lead distance of 2.5mm copper flexible cable from CT to relay is around 5mtrs.We would like to know the knee point votage(VK) & IM calculion for CT's

1974


how to find number of run cable laying[LT side] for transformer & alternator secondary side? [above condition for getting output power transformer to main panel side] give the example.

2123


what are the advantage and dis-advantage of 3 phase 4 wire energy meter?

2228


What is the function of Governor in Hydro Power Station? What is the Function of Lightning Arrestor Voltage Transformer (LAVT)?

2858


Pls tell me whether we can use EN3A material for shafts of Permanent magnet alternator.What will be the effect of magnetic and nonmagnetic material for shafts on magnetic properties of PM rotor .

3583


What is class ab operation?

1099


What are the types of windings present in the ceiling fan? What winding will be effective first when we started the fan?What are the resistance and inductance ratios comparatively at the initial speed and full speed of the fan?

3054


What is resolver and glass scale in CNC how they work?

2329