how to estimate the breaker capacity of breaker,please give
the one example( 6.6 kv breaker,800a)?????
Answer Posted / raghavendran.r
Step1: Calculate the system MVA.I have calculated that as 1.732*6600*800 = 9.144MVA. I have taken it as 10 MVA for easy calculations further.From the system MVA find out the Fault MVA value using the per unit impedance.i.e
Fault MVA = System MVA /P.u.Impedance.I am taking iot as .1
Hence we arrive at the Fault MVA.From this condition we get to know the Short circuit current as Isc = Fault MVA/Sys Voltage(6.6kV).
Usually, for a 6.6 kV system, the short circuit withstand rating is 40kA for 1 second.The Momentary current or making current is 2.55 times the Max. short circuit current.hHence we arrive at 100kA(Peak)
Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
Shall I use 40A semiconductor Fuses in 32 A SFU ? Frame size is same. What Happen if Fuses burn on SFU?
WHAT IS MOBILE SUB-STATION? & REALLY BENEFIT IN INDIA
if any body have question paper of railway (section engineering),then plz send me .i will thank of him/her.
If we want to change a contactor of faulty one what are the conditions want to fullfil
state the working principle of incondenscent tube?
if there are six generators (3 gas CATT, one Jenbacher o1 MW each, and two nos Diesel 01 no 01 mw other 0.65mw EDGs ( say), 3 CAtt gas set have identical pole pitch,01mw EDG and Jenbacher gas Set have different pole pitch, how their power connection can be done to connect a common bus bar during installation. in short, how different pole pitched generators power connection can be done to connect a common busbar system through generators incomer ACBs.
in cvt,there are two windings,1a,1n and 2a,2n.in my one project i use only one winding i.e.1a,1n. the other winding is not in use, so i connect it in open delta and want to close it by ibsertibg thermal resistor. the output of cvt is 132kv/115/sqrt3. plesae tell me exact value of resistor, so i may close it to avoid the resonance phenomenin. send me answer on this email adress please. aetcon-po@aetcon.com
how to deside the capacity of chock for drive?
What is milivolt dop test in Busducts? What is its significance & procedure to do the test?
Starting times for soft starter & power factor is thier any standard or datas available in manufactures list. Kindly suggest.
Can anybody tell abt concrete encased earthing or grounding?
how we findout a ignater is faulty or not?
How to select the cable and voltage drop in circuit?
Which cable is use for rtcc control panel
what is integrated ac contact circuit