Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I saw one P&ID 6" control valve has been connected with 8"
process line, and 2" valve also connected in parallel with
6" valve. why the 2" valve connected in parallel, Is there
any technical reason. please clarify. With Regards-Kittu

Answer Posted / ajith294

above answer is split range controller. what is a split
range control? two control valves are controled by a
controller is split range. for eg: 50% of controller out
put both of the valve will be close condition , see below
table.

% input Valve A opening %, Valve B opening&
0 0 100
25 0 50
50 0 0
75 50 0
100 100 0

but in your question on 2" valve is connected parrallel
with 6" Control valve. means for the bypassing 6" control
valve, they are using 2" valve.

for technically it is very very improtant. becasue at the
time of maintance of the control valve, there will be no
disturbance in process.

Is This Answer Correct ?    2 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how many types of viberation transmitter and how to calibrate and where use of vibration transmitter

2082


What are the uses of orifice plates?

1036


Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com

3162


Explain PID controller tuning & any one method used for it.

7694


what is KV and XV valve

1739


in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.

2751


Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75 The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is: WARNING: Could not connect to equalize destination. (7001) Retrying. Number of retries = 0/1 ERROR: LdXopsLoadMain: connect error 10060 ERROR: Processing terminated due to connection error. (7002) Equalization end with errors. STN0149 ---- ERROR = 2 WARNING = 1 ---- Background: >Updated the ExaOPC software on the STN from 3.60 to 3.75 >STN operating system is Windows Server 2008 R2 >HIS operating system is Windows Server 2016 Stanard Solutions attempted include: >Ensuring all IP addresses are correct and all networked devices can be pinged. >The ability to ping a device using its host name from another device ( from HIS) >Ensure both devices firewalls are disabled. >The antivirus installed on the STN is disabled. >Ensuring both devices are within the same workgroup. >Added both devices to each other's Host and LMHost files. >Running IT Security tool after changing any administrative settings.

2138


can we copy the software from a transmitter using hht(hart 275) ?

2014


what is the responsibility of an instrument commissioning supervisor

3099


Which is your favourite subject & explain any one topic of it.

9505


How digital input and digital output 's are working in dcs

2475


Q- What are the application in which PNP transistor is preferred over NPN ?

3288


What is the use of double seated valve?

1241


what are the values of fuel flow rate in various places in boiler.

1655


Explain pH, Conductivity.

2074