I HAVE A 1 MVA TRANSFORMER, I WANT TO KNOW THE FAULT LEVEL OF
THE SYSTEM ( WHAT IS FAULT LEVEL PLEASE EXPLAIN WITH EXAMPLE)

Answer Posted / shivakumar kinni

1 MVA, 11/0.415kV Transformer

Full load current= 1000000/(1.732x415) = 1391.24A

% Z(Impedance)=5 (As per IS 2026 for transformer ratings of
0.631 MVA to 1.24 MVA)

Fault current= IFL/%Z =1391.24/0.05 =27.824 kA

Is This Answer Correct ?    18 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is meant by tranformer impedance?

2156


List advantges of active filter over passive filter?

629


In a carnot engine with an efficiency of 40%, the heat rejected to the sink at 27 C is 60 kJ, then the heat supplied in kJ to the engine by the sources is

673


For a stable system, where should the poles of a system be in a root loci plot?

728


What is the formulae of Megger value for a A.C.Motor

2291






HOW TO CALCULATE AMPs OF CURRENT TRANSFORMER IN HT Panel

1802


Why arc quenching is used in Diode ?

1569


In Plumbing services What are accessories we consider for a bathroom?

1552


WHAT IS IEC? & WHAT IS BENEFIT TO PRODUCT FROM IEC?

1677


How to design pavement quality concrete by using C.R.C.P Method

1278


HOW TO CALCULATE ELECTRICAL, MECHANICAL,& OVERALL EFICIENCY OF GAS ENGINE POWER PLANT

1533


how can service sitting be setted for MCCB?Example for sittings IR (CURRENT RATING),IS(CURRENT STARTING)IO (current operating)?

1399


Sir, My doubt on cable sizing calculation, Load:74 KW calculated cable 1 run 50mm2. Now client asking us to reduce cable size by increasing runs. Sir, My question now when my mind strikes with 2 options 1) Divide load 74/2 = 36 and calculate cable for 36+36 making it 2 runs or 2) Simply i can divide 50mm2 /2 ie. 2 runs of 25mm2 Please suggest me sir

1428


why the perameters of secondary circuit are more important then that of the primary circuit of induction motor?

1373


How generating electric power export to grid from the generating station ?

1409