Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

In a 11kv/433v transformer,at the LT side ie 433 V side why
do we need to put 3.5 core Cable upto Panel.The full load
rated Amps is 666 at LV side.What value of current will flow
through the Nuetral Conductor.Why can't we use 4Core Cable
instea of that?

Answer Posted / hanmanth reddy y

In a three phase system with star connected secondary
(433V side) if two phases are fully loaded to 666A and the
third phase not at all loaded the current through nuetral
conductor will be 666A. But in practice in a three phase
system that the third phase not having any load and other
two phases fully loaded is not in practice. If all the
three phases loaded equally no current flows through
nuetral and nuetral cable is not required.

Based on the requirment of transformer insulation nuetral
earthing has to be done at the transformer terminal only.

Nuetral is neccessary for single phase loads. If the
nuetral is dispensed entirely it is not possible to supply
power to single phase loads. Normally even in worst case as
huelistic judgement the nutral current will not exceed 50%
of phase current under unbalaced load conditions. Hence it
is appropriate to select cable of 3.5 core rather that of a
4 core cable.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Is better to supply the voltage for static exciter from the auxiliary power source or from the SG terminals? And why?

2001


I am going to appear for the RRB Chennai junior Engineer online exam. Please send me the previous exams question papers (also solved) to my mail id: rrkhandhar@yahoo.com

2046


how to interlock 3 incomer-ACB,1 buscoupler ACB,... pls answer this question and if possible send me the ckt diagram..haifriends2910@gmail.com

2967


What is milivolt dop test in Busducts? What is its significance & procedure to do the test?

2137


1)Explain why the cradle guard is used on railway crossing in overhead line construction?

5110


hi friend i am going too attend for hpcl in this month please help me by sending written test question papers i am in the stream of E.E.E

2021


How to measure size of cable on a given load

1905


Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?

1865


HELLO EVERYONE, I RECENTLY HAVE FOUND ONE PROBLEM, I WAS TAKING NO LOAD TRIAL OF AN HT MOTOR 920 MOTOR , 1440 RPM , 6.6 KV, WITH AUTO TRANSFORMER. AT 450 V, LOAD WAS 40 AMP AND SPEED WAS 250 RPM. BUT AS WE INCREASE VOLTAGE FROM 450 TO 480V, LOAD BECOME 41 AND SPEED REDUCED TO SOME RPM . SO WHICH PHENOMENON ACTED HERE FOR REDUCING SPEED.?? AND IS IT HAPPENING ALWAYS OR IT IS RARE? I ALSO HAVE FACED SUCH PROBLEM WITH FEW LT MOTOR ALSO.

2000


What is the most important precaution in any experiment with d.c. Shunt motor?

1308


The power supplied to a 33microF capacitor from a 120V, 60Hz source will be

2207


i have flexible wire. size of conductors is 0.190 mm & no.of conductors are 48. then size of wire comes 1.37 sqmm instead of 1.5 sqmm . the what is tolerance for this size.

1856


How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?

2036


my UPS suddenly goes off and all panel light also blow off.This happens even main electric supply is not interrupted.After some time it automatically starts functioning normally.Batteries are new.

2114


What is the significance of integral controller and derivative controller in a pid controller?

1236