In a 11kv/433v transformer,at the LT side ie 433 V side why
do we need to put 3.5 core Cable upto Panel.The full load
rated Amps is 666 at LV side.What value of current will flow
through the Nuetral Conductor.Why can't we use 4Core Cable
instea of that?

Answer Posted / hanmanth reddy y

In a three phase system with star connected secondary
(433V side) if two phases are fully loaded to 666A and the
third phase not at all loaded the current through nuetral
conductor will be 666A. But in practice in a three phase
system that the third phase not having any load and other
two phases fully loaded is not in practice. If all the
three phases loaded equally no current flows through
nuetral and nuetral cable is not required.

Based on the requirment of transformer insulation nuetral
earthing has to be done at the transformer terminal only.

Nuetral is neccessary for single phase loads. If the
nuetral is dispensed entirely it is not possible to supply
power to single phase loads. Normally even in worst case as
huelistic judgement the nutral current will not exceed 50%
of phase current under unbalaced load conditions. Hence it
is appropriate to select cable of 3.5 core rather that of a
4 core cable.

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to select HT/MV cable size ?

2005


PIU how does work?

1996


How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter

6725


how does high earth to neutral voltage affects electronic circuit?

1300


Star Delta Diagram with full description

1908






how to do the ductor test?

6565


If SFU is Switch Fuse Unit, What is the expansion for FSHF in Electrical Engineering?

2065


We have 5 Distribution sections with variable loads&We have 3 Gensets(500kva,380kva&250kva) our total load is between 400kva to 600kva. so how could we connect 3gensets.

1427


Transformer diagram mention each parts ?

1587


How to do cable earhing? whether by grounding Armour to ground or by running extra G.I wire along with cable? which one is preferred mostly amoung them? If the second one is more preferable how many GI wires to be run along with cable (1 or 2)?

1597


Difference between drift current and diffusion current?

1318


what is the problem when i want to close a circuit breaker by local position it closes well.but when i close it in remote position it trips

1088


What does the term supermesh means?

671


sometime battery charged and then automatically charged when rectifier ON conition, is there any chances please clarify the same.

1383


What is the effect of interchanging core(made of steel) and winding(made of copper) material in case of transformer? Give proper explanation in regard to different losses in transformer.

1435