Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we calculate the capacity of the capacitor bank
attached with the Main panel, when we know the capacity of
the panel installed in KVA Rating?

Answer Posted / sanjeev nair

The formula for calculating the Capacitive kVAr required to
compensate inductive kVAr is kW*sqrt(tan_angle1-tan_angle2).
In your case, you have to check the present power factor
and then the kW.
Suppose, If you have load of 50kW and the power factor is
0.8 and you have a plan to improve the PF to 0.95 then as
per the above formula the Capactive kVAr required to
compensate the inductive kVAr would be 21.
Besides, one should understand and work on the application.
ie, you can go for a 20 kVAr capacitor bank as per the
above if you have 50kW motor working on a pf of 0.8. If
both load and inductive kVAr is varying, then you have to
go for automatic pf control system with suitable banks to
compensate the inductive kVAr.

Is This Answer Correct ?    4 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHY THE COLOR OF OUTDOOR TRANSFORMER IS BLUE ONLY???

2169


in power generator normaly voltagr betwween esth to neutral is 0 but my work place generator show the volatge is 60v any body know why? thanks

1945


what is meant by neutral compensation factor and where it is used

1960


What is the Good Earth resistance value of G.I & Cu. Chemical Earthing & Normal Pipe Earthing?

2382


How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?

1964


Grid fault level [KA]?

2657


what is meant by carrier aided trip protection in transmission line

3982


Draw a SLD of DG distribution up to main LT panel?

9528


Why 9KV surge arrester having 7.65KV of MCOV?

1629


What is relation between mu(nought) and epsilon(nought)?

1591


what is the difference between an alternator and a synchronous motor

2069


What aturn on methods of scr?

1232


i am venkat i got gre 930(verbal 270 quanta 660) and my toefl score 105..here question is why u got less score in gre ? what i supposed to tell...any chance of rejection is there...my accadamics record is very good

2192


Hi Friend I am used multimeter to measure the voltage between R Phase(SS1) to R Phase(SS2). In SS1 is connected with UPS loads. But I am getting voltage between these 2 R Phases. Please give some idea friend

2160


can i use 2000/5A Clamp meter to measure HT cable

2072