What do you mean by pf of a generator? Power factor purely
depends on the load (wether inductive, reactive or unity)
then what does the pf mentioned on the generator nameplate
means?
Answer Posted / madhusudhan
Kw= 1.732X Voltage X Current X pf. in these parameters only
current and pf are variable. The current limitation given on
the DG set is at that pf. if pf increases the current will
get decreased for the same KW. so you should monitor the
same pf as mentioned of DG set name plate or else you should
reverse calculate the current limitation at your load pf and
monitor the DG set no to get overloaded.
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
How earthing of switchgear system to be done.
can any one provide me a connection wiring diagram for a DG set control panel along with BOM?
what is the condition for YnD11
what is meant by skew width in machines?
How can a equal potential zone be carried out in conductors?
What is the meaning of utility ground and clean ground? How the distribution panel is grounded?
How many kw will suply from one db
What types domain of laplace transforms? What behavior can laplace transform predict how the system work?
Does all the output contacts (N/O as well as N/C) of a Numerical relay operate when relay receives a binary input/inputs or contacts are designated to specific logic input/inputs and only these contacts operate?
why do motors burn out? I understand why adding parallel loads to a power source means more current moves through the circuit, and can destroy circuit elements by overheating. What about when you have a vaccuum cleaner intake flush against a floor, a room fan sitting directly against a wall, or a power drill trying to drill through something too hard?
What are the characteristics of negative feedback?
How to calculate the volumetric capacity of a oxygen & Nitrogen gas Cylinder if pressure is 145 kg/cm2 & water capacity of cylinder is 67 liters.
Fantio of tranformer
How much kv gas generator is needed to run 2 hp and 1 hp airconditioners, plus a refrigerator and 4 Tvs
for compensate 315mh inductance ,how many capaciance required?