Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

1,why we use 4-20 ma output of all instrument qhy not use 0-
20,
2,what is the different between PLC & DCS.
3,how can we meaure maximum span of new flowmeter if not
given any information.

Answer Posted / rohan g

0 to 20 vdc signal may detoriate over distance but current
signal will remain intact.
noise will not affect current signal at all but vdc signal
will get affected.
if equipment fails then also it gives 0 vdc signal in case
of 1 to 20 vdc.but not in case of 4 to 20 ma.
DCS can be viwed as bigger version of PLC.Since no i/p dcs
can support is more in case of dcs.Also dcs can have
operator interface but plc dosent have such.

Is This Answer Correct ?    17 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What happen if we install my pressure transmitter below the elevation of pipe in natural gas service?

1065


What is cut off relay? And why use in PLC and DCS?

1376


How is PH sensor works ?

1973


wich is coming the first HAZOP OR SIL

2763


NSV type probe stands for

2392


How vortex sensor used for steam flow measurment can be checked on line i.e without taking out from process line.

2150


if in a level tx height is given, how u calculate the ranges of the tx?

7733


What are primary elements of measuring pressure?

1292


what is dc moter.

2235


How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.

1711


What is the purpose of bypass valve across AS valve.

2110


Capacitance, resistance ( colour coding ), parallel & series circuits.

2230


Hi i m B.E. In elect. & comm. I m workin in bio mass plant from 6 mnths as inst. Engg. but now i m in dept. Of operation as shift engg...which is best operation or inst. 4 me? M confusd..plz help and reply me..

4258


How many types of sensor

1621


If i have 4 Allen Bradely make RS logix 5000 PLC and for viewing that we are using 4 RS view SCADA for 4 different packages. Now, I will want to view two packages on only one SCADA. Then how i will do it?

2386