For loop checking we are having ILD (instrument loop
drawings)as a documents. for AI we give 4-20ma and chek in
the system if accordingly raw count is coming or not.
for AO we force from the system and check in the plant if
according to raw count current is coming or not.
for ESD loop checking raw count in the system(Triconex) is
819 - 4095 i.e for 4-20ma
if there is problem is loops then we go for backward
checking i.e from system to know where is the problem.
then we do point to point checking.
after completion of loop test we go for functional test.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Tell about your IFFCO plant visit.
Decibel.
Name different parts of a pressure gauge.
Why thermo wells are used? What materials are used in thermo wells?
principle of automatic votage regulator
what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .
What is the PLC configuration in Cement industry?
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure
Explain the working of rota meter.
Please tell me details about Sox,Nox,SWAS analyser????
What is the right procedure for adjusting the gap voltage of bently nevada vibration sensor?
how to commission furnace ( water heater)
We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.
HOW TO CALCULATE ACCURACY OF AN INSTRUMENT. WHICH IS COMPITABLE FOR USE.
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.