how to do loop checking pls email to
shanavaska2000@yahoo.com
Answer Posted / rahul
For loop checking we are having ILD (instrument loop
drawings)as a documents. for AI we give 4-20ma and chek in
the system if accordingly raw count is coming or not.
for AO we force from the system and check in the plant if
according to raw count current is coming or not.
for ESD loop checking raw count in the system(Triconex) is
819 - 4095 i.e for 4-20ma
if there is problem is loops then we go for backward
checking i.e from system to know where is the problem.
then we do point to point checking.
after completion of loop test we go for functional test.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is compensation for flow ? Why we use compensation ? What are the factors of different compensation ? We not use then what problems may happen ?
How to calculate P,I&D value in PID controller ?
What is motion balance principle?
How the sizing of the analog signal cable is calculate?
Describe the function of Accumulator into the Pump
what is wave length were using ?
State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.
In turbine what does term CDP, NI, NH, HSSOC means.
Can Any body tell me how to check Modbus Settings in ER300N L&T trivector meter?
What are the different types of thermistors used in industries? How to the operation of typical thermistor?
What is the differerence between hysterisis and linearity.
If P will increase then what will happen with PID?
Specify ideal accuracy of flow element like orifice plate, Ventury, Annubar. Ultrasonic flow meter etc.
Explain the working of an electronic level troll.
can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.