How to measure corona loss in a transmission line?(Plz ans
only if u know the exact answer)
Answer Posted / roysayan01
well let me answer my own question-
I'll let you know,measuring Corona loss is no child's
play.Even if you are well equipped in the field of power
transmission, errors would creep in.
The expression for corona loss is given by
Peek's equation
Pcl = (244/q)*(f+25)*(Sqrt(r/D))*(Vph -Vd0)^2 * 10^ -5
Kw/Kw/phase
You think that's complicated? There is more to come.
In the above expression r is the radius of the wire in
meters and D is the effective distance between the wires in
meters,f is the frequency of transmission voltage,Vph is the
voltage to neutral or the phase voltage and Vdo is the
Disruptive critical voltage.
q = Air density factor which is given by expression
((273)/760)* p/(273+t)
All the calculations for q are done by converting
temperature into Kelvin scale
273 K in the Standard temperature and 760 mm of mercury is
the standard pressure and they are taken into consideration
in the above expression.
p is the atmospheric pressure when measurement is to be done
and t is the temperature in degree celcius at that time
The expression reduces to q = 0.359p/(273+t)
Hold this tight we'll get back to it later on
Now we need only Vdo or the disruptive critical voltage(The
voltage at which corona effect occurs) to calculate the
corona loss
Vdo=go x m x q x rx ln(D/r)
go is the breakdown strength of air.It's about 30KV at
normal temperature.
m is the irregularity or roughness factor of the condutor
which is a given thing.
q is Air density factor which as discussed above
and D and r are the effcetive distance between conductors
and the conductor radius.
No we have all the required things to measure corona loss.
Putting all the values in right place in the Peek's
equation, we get the corona loss.
hope i explained the whole process vividly.
| Is This Answer Correct ? | 7 Yes | 1 No |
Post New Answer View All Answers
What is the polarization index value ? (Pi value)and simple definition of polarization index ?
what is PDU in transformer?? which company manufacture??
how net resistance islow in star connection and viseversa in delta connection...? if anybody could explain in detail it wud be helpful.
Application Comparison between 22KV (UE)and 33KV (E) system. Are we allowed to use 33KV (E) cable in lieu of 22KV (UE) cable. What are the technical disadvantages.
hi guys please tell me the procedure for mesuring the coil resistance of 3ph induction motor?
what is the VA(Volt-amphere)? define with calculation?
how to carried out DAR test in 11 KV Alternator ?
Ac generato how produce power I need for camplet defination
WHAT IS THE TECHNICAL SPECIFICATION OF C CURVE & D CURVE LEGRAND MAKE MCB
Name the component u would expect to find in a switchgear assembly?
How to test Alternator stability test for REF relay
What is the effect on power factor, shown by a trivector meter; incase of reverse phase sequence. If the power factor of a system is lag what meter will show in case of reverse phase sequence connected to the meter. and What in case of lead.
why single phase to grd test in HV cable?why not 2 phase at a time?
give me atleast four differences between circuit and network
brief notes on ammeters