We have 800KW motor operating at 6600Volt,50 Hz
supply.During 1st startup it tripped on overcurrent
trip.It's FLA is 88 Amps.The K factor of Thermal overloaaad
was set on .94 initially.then we set at 0.97 and then it
started fine.i dont understand why it tripped first?What
are the protections which comes in picture during starting ?
Answer Posted / ghani
It is right that starting current of this much big motor is
very high whihc varies as per data from 6 to 8 times, so if
the protection relay is of static or digital then there
must be a restraining setting for starting current with
time delay, so you can increas both values keeping the data
sheet of motor in view.
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
What is the temperature PROFILE OF A FLUID W. R. T. Distance from a sphere to which it is IN CONTACT which is at constant temp.?
What are stable systems?
what is resver in electrical enginnering with answer
Advantage of LT panel vs HT panel
When a single pase capacitor run motor- run on 230vac and Case(1)run with 8 Mfd 250 vac.capacitor , Case( 2) run with 8 Mfd 400vac capacitor. What is difference between both case regarding power ,efficiency etc?
How to do cable sizing calculation for 750 A Neutral Earthing resistor for 33kv. the 33kv cable going to swbd. is 630mm2 3 runs.
how i chosse capacitor bank if my energy meter is 48 kvr? tell me capacitor bank chossen formula?
i want wipro vlsi placement pattern please send me
I need model question papers for RRB section engineer Chennai... Please send to my E-mail Id:- maitheerainbow@gmail.com
what is class of SPD and dittels of all class ?
hi , i have 150 kw loud and we need 50 m cabil,i want to know wich size cabil we use. thanks
how to electrically make connection to ferroli GN2N?
What is the feedback in the control system?
What is real time power factor control panel(RTPFC)?
do we use neutral grounding for resistive balanced load? if we use what happen?