We have 800KW motor operating at 6600Volt,50 Hz
supply.During 1st startup it tripped on overcurrent
trip.It's FLA is 88 Amps.The K factor of Thermal overloaaad
was set on .94 initially.then we set at 0.97 and then it
started fine.i dont understand why it tripped first?What
are the protections which comes in picture during starting ?
Answer Posted / ghani
It is right that starting current of this much big motor is
very high whihc varies as per data from 6 to 8 times, so if
the protection relay is of static or digital then there
must be a restraining setting for starting current with
time delay, so you can increas both values keeping the data
sheet of motor in view.
| Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
how to calculate slip ring induction motor stator and rotor currents??
i have a 1500kVA transformer what is the kWH meter i need to use?
what is doid
What is the type of feedback used in an op- amp schmitt trigger?
How could a garment factory benefit from renewable energy
What is the difference between Generator Differential Relay and Transformer Differential Relay?
what mean by analog ,digital,numerical meters and relays? say the example?
how to calculate single phase motor efficiency ?
what is the voltage regulation for unity and zero power factor?
What is the mechanism of WTI
what happens in the short circuited secondary transformer,if the resistance of the short circuit is increased gradually?
Sir pl provide 5 year sample paper for post junior engineer(electrical).I have currently applied for junior engineer (electrical) on RRB Ajmer
Can any body tell me the different types of LT cables & their application.
Is there any relevant technique to produce power from light and heat energy of the sun simultaneosly from same rays of light?
Distribution transformer we provided 2 separate earthing pit for Body and 2 separate earthing pit for neutral,we can not connect separate body earthing pit to other earthing pit but we do metal glanding in secondary side cable termination in both side, transformer and PCC panel (LT Panel), is this safe for transformer and other equipment?