Dear sir/mam
Iwant complete details of Naintenence of 33kv/433v
Transformer having 1250 KVa
Answer Posted / virendra1981
Dear friend,
In routing maintenance you should take care of the
following .
Daily .
1. Percentage loading of a transfomer
2. Make sure the bucholze realy is full with oil no inert
gas is there if there then purge the same.
3. Check the record the Reading of OT & WT
4. Check manualy for any leakage from any part of the
transformer.
5. Check for any abnormal heating & noice in transformer.
Quarterly.
1. Check & change the silica gel of the breather .
2. Check teh Safety function tripping of HT breaker related
to transformer. ( tripping point of OT , WT & Tranfomer )
Annualy.
1. Check & fillter the Trasformer oil
2. with complete shut down take the reading of insulation
resistance of the transformer winding.
3. Open & check the condition of transformer HT & LT
bushing for any cracks or damage.
4. Chceck the condition of the earthing pit & take the
earthing resistance value for all the earthing pit (
Neutral & Body earth )
Do the same as directed & have a trouble free operation of
the transformer for a long period of time
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Whether the vacuum contactor requires Short circuit protection?If No,why?
What happen in ups if phase reverse?
ratings of lightning arrester
calculate external resistance values to add to the rotor of a slip ring induction motor. STATOR- 415 V, 3 phase delta, 1100 A, 50 Hz, 1490 rpm, pf 0,86 ROTOR - 660 V, 590 A, 50 Hz. STATOR current at each steps STEP1-600A,STEP2- 800A,STEP3-1000A,STEP4-1100A.
How many types of electrical earthing are there?
how the characterstics of control valve being done
How can we calculate ac current from the given DC current when AC voltage is given?
what is mean by NPS (Negative phase sequence)fault? what is the difference between EFR & OCR faults?
What are the temperature elements?
specific difference of ICT&Auto Transformer
What is the difference between the transmission line and distribution line?
why we are using earth pit in sub stations.?
Why compensation is necessary in feedback control system?
what is the minimum requirement gigaohms for the insulation test using 5kv in 300mm xlpe cable
Determine a suitable number of slors and conductors per slot for the starter 1 winding of a 3 phase, 3300 V. SO Hz 300 rpm alternator. The diameter is 2.3 m