How to Calculate the maximum Demand required for a
connected load for a manufacturing Plant
Answer Posted / mior
First of all, you need to know your total connected load
(TCL). Then, you apply Diversity Factor at your TCL to get
the Maximum Demand (MD).
Example;
You have 1no. 36W Florescent Lighting and 1no. socket outlet
(250W). Your TCL will be (36W + 250W) = 286W.
In actual, the TCL may only contribute certain percentage
for your MD; that's why you need to apply Diversity Factor
(DF).
Common practice, light fitting will contribute 80% and
socket outlet giving 40% for your total MD.
Hence, your total MD will be = [(36W * 80%)+(250W*40%)
]= 128.8W
Therefore, your total MD to be declared for your Utility
Provider will be 128.8W.
The link below might help your for more info.
http://guide4electricalconsultant.com/calculate%
20tcl&md.html
Is This Answer Correct ? | 72 Yes | 13 No |
Post New Answer View All Answers
How can we findout the maximum efficiancy of Transformer? At which load?
how to calculate IR value of 33KV cable ??
if we run a 3 phase machine on two phase what will happend??? given answer with solid reason please
What is oscillator circuit?
What facility we get after CT secondary earthing and how?
how does a liquid starter reduce the starting currents?
What is the abbreviation of NGT panel
What is meant by short-pitched winding?
Does the motor power displayed on the Motor name plate is the mechnical power motor delivers or it is consumed power from the system?
what are the different methods for the starting of a synchronous motor.
1.main parts of generator? what is used A-check,B-check,C- check? 2.what is FM200 system in data centers? 3.difference between pac,ahu?
how can we select the appropriate VCB ?
PAC and simple Ac different
What if the difference beween internal and exrteranal LBB?
Why sometime AVR and sometime Booster coil is used in Alternator? what is the diferance between AVR & Booster coil due to which they are selected