Two alternators say 1 & 2 are poised to parallel operation.
But at the time of paralleing alternator 2 gets out of the
system by tripping Earth fault relay. Please send me reply
why this is happening?
Answer Posted / jyotirmoy das gupta
The answer depends on the following parameters: 1. At which
point the two generating systems are earthed, 2. Is there a
neutral isolation for the second generator, 3. how the
earth fault sensing element is connected- by 3 phase CT
forming residual circuit or direct measurement placing the
CT between generator star point and earth, 4. what is the %
setting for earth fault protection and what delay is
setted.
| Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
What is the method to solve circuit using source transformation?
EXPLAIN WHY THE SURGE CURRENT RATING OF AN MCCB OR CIRCUIT BREAKER DECREASES WITH INCREASE IN THE RATING OF MCCB OR CIRCUIT BREAKER.
what is PDU in transformer?? which company manufacture??
why normally Generator rating are between 11Kv to 22Kv?
how we findout a ignater is faulty or not?
A cable with concentric PE conductor must be used with frequency converter circuits what does its means.?
how to measure the transformer resistance values(dyn11)?and howmuch the minimum value?
What if the difference beween internal and exrteranal LBB?
HOW TO TEST A LIGHTENING ARREST ER ?
Is there any Institution for giving M-tech in Electrical engineering for those who r in service? Give the details please.
how to interlock 3 nos MCCBs using under voltage coil. please provide me circuit diagram?
What is MS-EXCELL?
any one guide me to reduce the power factor of diesel Generator from 0.97 Leg to 0.8 Leg.with out any change in my load.
difference between the applicability of nortons and thevenin theorem
Post possible questions for Power Factor Panel FAT / SAT