Two alternators say 1 & 2 are poised to parallel operation.
But at the time of paralleing alternator 2 gets out of the
system by tripping Earth fault relay. Please send me reply
why this is happening?
Answer Posted / jyotirmoy das gupta
The answer depends on the following parameters: 1. At which
point the two generating systems are earthed, 2. Is there a
neutral isolation for the second generator, 3. how the
earth fault sensing element is connected- by 3 phase CT
forming residual circuit or direct measurement placing the
CT between generator star point and earth, 4. what is the %
setting for earth fault protection and what delay is
setted.
Is This Answer Correct ? | 3 Yes | 1 No |
Post New Answer View All Answers
3Cx240 & 3Cx300 sqmm Al. cable from lv side. What is the calculation for this cable??
what would happen if reactive power (kvar)is increased (more)or decreased (less)? how much exact reactive power should be maintained? and what should be done for that
Q: How to calculate Transformer losses , tell us by Formula.
Mention the methods for starting an induction motor?
how to introduce yourself
What is the implications when 600 hp motor is started when the unit is running with Transformer of capacity 1500 KVA and DG set of 1000kva
What is a difference between indoor transformer and outdoor transformer of same rating
why co incidence factor considered in transformer sizing?
What is the difference between the impedance percent and impedance voltage ?
What are the basic properties of signal flow graph?
WHAT IS DIFFERENCE BETWEEN CAPACITOR AND CAPACITANCE?
What is the meaning of 40X8X2 busbar dimensions for carring load of 400 Amps
why incomer bay is required before transformer bay if there are more than 1 nos. of transformer bay.
Difference between HRG and NGR. Are they both the same thing
any one can explain the stages of a knee point which is taken during ct magnetising curve.