what happen "when Dyn11 is parallel operation with Dyn1"?
Answer Posted / dubai
I agree with murali.
Transformer having -30˚ angle (here DYn 11) can be
paralleled with +30˚ (here DYn 1) angle by reversing the
phase sequence of both primary & secondary terminals of one
of the transformers eliminating phase angle errors.
| Is This Answer Correct ? | 3 Yes | 0 No |