i have one transformer 1000kva, 11/.433kv. we are using
200/5 amp. ct unit for measuring purpose, & one 800 amp.
V.C.B Unit for the same t/f operate, i wants to known the primary
current of T/F is only 53 amp. why we used 800 amp.
V.C.B ? & 200/5 amp. CT Unit.
Answer Posted / vinit patil
You are right, you should fight with your electricity board
regarding the HT Metering CT ratio. You should actually
required 100/5 ratio.
But while deasigning VCB it is always prfarable to go on
higher side because it can sustain the heavy short circuit
current. One thing should be noticed that the protection
CTs should be as per the Primary current of the ransformer.
| Is This Answer Correct ? | 5 Yes | 2 No |
Post New Answer View All Answers
For some transformers we are using solid neutral earthing while some others we are using resistance earthing why ?
Why a Permanent Magnet Generator has higher frequency as compared to frequency of main alternator?
Differentiate between magnetic field and magnetic flux?
What is meant by rotor?
sir plz send some previous year questions of jspl.
Good day everyone,currently in our premise we using 30kw slip ring motor with resistance bank which we use as forward and reverse at conveyor bar handling. So,my question is how do we calculate the resistance bank which is suit the motor. Kindly,assist me... thank you
How to calculate Air conditioning capacity for a telecom BTS shelter?
How can we measure earthing resistance test (Earth meggar) of Transformer neutral pit while in live condition?.
Define newton's law of viscosity.
Hello Friends, How can we recognize the CT Star Point is S1 or S2 in case of Electro Mechanical Relays and what is meant by Restraining coil in relays and what is the purpose of that.. thank you in advance..
What is the previous name of Cox's Bazar
A cable with concentric PE conductor must be used with frequency converter circuits what does its means.?
define the active power?
percetans
how does commutator convert a.c to d.c?