Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how we can select a transformer based on a particular load.
suppose we have 4 motors of rating 40 h.p , 50 h.p, 80 h.p
& 100 h.p. then what rating of transformer we can select.
urgent. pls reply

Answer Posted / mayank goel

40+50+80+100
=270HP
1 HP=746Watt
270HP=201.42KW
Power Factor@.7=287KVA
Loading on Transformer 85%=337KVA

So we can use 400KVA transformer for this motors is okey.

Is This Answer Correct ?    23 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

CT Ratio of a energy meter connection is Red Phase : 100/5A, yello Phase : 50/5A & Blue phase : 100/5 A what is the overall Multiplication factor

1662


Does outdoor isolator loose connection cause short circuit current in that circuit? if yes then how ??

1704


what should be correct gas pressures to be a 1.5 ac unite

1509


how to carry out Magnetizing Current Test on Distribution transformer and what purpose we are doing this test. why transformer rating in always in KVA ? what ispositive, negative, zero sequence impedence? How ElCB tripping if Neutral touch with ground Why AC & DC capacitor are use in UPS ? why motor rating in KW? how to syncronize two dg sets

2199


reason of diode failure in alternator

1869


i have flexible wire. size of conductors is 0.190 mm & no.of conductors are 48. then size of wire comes 1.37 sqmm instead of 1.5 sqmm . the what is tolerance for this size.

1797


xpression 'document.FrmQF.myemail' [

2007


what is the purpose of shading ring or shading coil in electrical equipments.

4484


how are reversing the direction of dc motor

1662


how to find out cable size if load is 2800 watts, 230 volts AC supply and load distance is 1800 meters

1612


Define conversion efficiency of a power amplifier.

1250


Explain using drawings what is reverse PID action w.r.t PID controllers.

3462


when we decide to use soft starter drive or vfd drive in mcc to operate apump?

1991


in what type of applications v can use q meter?

2150


What will happen if the d.c. Shunt motor opened accidentally running on no-load has its shunt field winding?

1484