I have 1 KW, 3ph. 440v, 50 hz, cos(phi) .75, efficiency
75%(star delta connection)Motor. How to calculate line
current & Phase current (1) Star connection (2) delta
Connection
Answer Posted / s c budhiraja
(1) First for star connections:line
current=1000/.75*1.73*.75*440=1.75 A for both line &
phase.
(2) For delta connections; Line current=1.75A
Phase current=1.75/1.73=1A
Note: There no use of Motor efficiency here.
| Is This Answer Correct ? | 7 Yes | 3 No |
Post New Answer View All Answers
How to calculate the fuse rating depend upon the DC circuit?
why cable i burning without tripping. how can protect led street lights
Why there are some equipment(i.e:TV) that using 2-pin plug instead of three? What happen if there is current leakage? Are we going to get electric shock??
Explain advantages of storage batteries
How will you utilise electrical power? You can start from the generating station.
what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load
what are the applications of PLC?
WHat is the general checks required for Dry type transformers
What is the different types of cable & current capacity of cable
What type of pipe material G.I or M.S is used for sprinkler system?
Can any one give an explanation about rating factors of cable? if we are laying the cable on the air with an temp 15 degree then rating factors will be 1.15 and if we are laying the cable on the air an temp 60 degree then rating factor will be 0.76 please describe it and what is the difference between rating factor and derating factor?
What is magneto on a gas generator. how it functions. its out put is d.c or a.c. how it can be checked for correct functioning
Why derating factor os applied on Cables?
Why are cables rated for 40 KA for 0.25 Sec fault current rating?
What will be the impact on motor performance if a LT motor is rewound with changed motor winding data as given below:- Original winding data: total 04 wires = 02 wires of 17 SWG + 02 wires of 16.5 SWG. Changed Winding data: total 03 wires of 15.5 SWG wire size Motor rating: 160KW, 740RPM, 415V, ID FAN application. Normal Running Current = 95% of FL Current.