Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is pf. how to calculate capacitor bank value to
maintain unity pf.

Answer Posted / ezzuddin

SORRY FOR THE ABOVE WRONG INFO AND The correct answer AS
STATED below is the proof of the formula:

KVAR= MAX Demand X [TanQ1 - TANQ2];
TanQ1= [Sqrt(1–(CosQ1)^2)]/CosQ1
TanQ2= [Sqrt(1–(CosQ2)^2)]/CosQ2

The proof:
Pythagoras Theorem states that in a right-angled triangle
the square of the hypotenuse is equal to the sum of the
squares of the other two sides.
so that:
C is the hypotenuse.
S is the opposite.
P is the adjacent.
TanQ= opposite/adjacent = S/P -----> S=P x(TanQ;)
Pf=CosQ;= adjacent/hypotenuse = P/C ---->C=P/CosQ;
Pythagoras said that:
C^2= P^2 + S^2
P^2/(CosQ)^2= P^2 + (P^2 x (TanQ)^2)
by divide P^2:
1/(CosQ)^2 = 1 + (TanQ)^2
by changing the both sides:
(TanQ)^2 = (1/(CosQ)^2) - 1
(TanQ)^2 = (1/(CosQ)^2) - ((CosQ)^2/(CosQ)^2)
by Taking the (1/(COSQ)^2) Common factor:
(TanQ)^2 = {1/(CosQ)^2)} x ( 1 - (CosQ)^2)
by taking the square root:

TanQ; = [Sqrt(1–(CosQ)^2)]/CosQ;

so that:
KVAR = KW x [TanQ1 - TANQ2]

example:
PF1 = CosQ1 = 0.8
PF2 = CosQ2 = 0.92
TanQ1 = 0.75
TanQ2 = 0.426
P=1000 KW
Max Demand = 1000x0.8= 800 kW
Capacity of the required Capacitor= 800 x(0.75 - 0.426)=
264 KVAR
We proposed automatic capacitor= 300 KVAR

Is This Answer Correct ?    4 Yes 4 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Define cuttoff frequency?

1134


if 3400kw slipring motor rotor shorting done and motor started on mv drive ,what will be the rotor shoring current

1798


State thevenintheorem?

1110


Please, if 1kw is equal to 1.25kva; how then do I know how many kva in 7.5kw?

1732


how to select correct size of power cable for inverter duty motor

1638


how generator avr give to the input?

2058


What is miller crystal oscillator? Explain its operation?

1166


Why induction motor is widely used in industry

2817


How to select the cable and voltage drop in circuit?

1834


what is the safe meggar values for motor, transformer HT, LT and Cables? IF we want to replace I/C bay at our 220 kv substation which is of 140 mw load capacity bay to be replaced by 400 mw capacity bay.other than CT(1200/1) what are the other equipment i have to replace. why we generally use 3.5 core cable or in other word 1/2 core for neutral and also confirm me that in balance conditiob(3 phase)current in neutral will zero

2322


how invertor convert the dc into ac give brif detail

2225


What does the term supermesh means?

1257


What is difference between slip rings and carbon burushes?

15240


sir& friends i want the collection of recent quetions asked in interview of top most companies please send me on my email san.jsr@hotmail.com

1861


why electronic instruments is more favorable than electrical?

2021