what is the maximum load on for 10 kva & 25 kva transformer
Answer Posted / aruloli
Dear Friend
You forgot to furnish few more data i.e Voltage rating of
primary and secondary.
If i assume Voltage rating for 10 KVA Transformer as 230
V/110 V (Primary/secondary)and considering as single phase .
primary load current is calculated as
P=VI
10*1000(VA)=230*I
I=43.47 A
Secondary current is ,
90.90 A
Considering Transformer as 3 phase, then
P=1.732*v*I
Primary load current is
10000=1.732*230*I
I=25.10 A
Secondary is,
52.48 A
| Is This Answer Correct ? | 35 Yes | 15 No |
Post New Answer View All Answers
Advantage of LT panel vs HT panel
what is acceptable leakage current for 33kv cable while doing high voltage test for cable? how to calaulate the leakage current for 33kv or any rated cable?
define as synchronous generator
On 400 amp factory load how kvarh capacitors provide
what is interpose? where it is used and why it is used?
diff b/w normal grounding and resistance grounding
what is the differation bewreen kwh & fundamental kwh in electronic trivector meters
What is highest size of HT motor like 11 kv or 33 kv,and how to make it 750 rpm.i think the size will be very big.any idea ? pl. reply..
when we have to purchase the transformer by own i.e how much load will preferred HT connection?
In case of generator when we consume more power produces by it why load on generator increase and starts sound more. and how it is adjusted..
15hp motor wound by 0.9mm & 0.95mm magnet wire. at no load test it draw 4.2A current. Another motor with same condition draw 9.2A current. How can that occur? pls help
how many single tension hardware are required on a double circuit transmission tower?
How could I get a certificate of competency as Electrical Supervisor? I have completed By BTech in Electrical this year(2012) for VJTI Mumbai Maharashtra. Is it compulsory to be produced while joining?
Differenciate between circuit wiring and sub main wiring with illustrations
Please give me a erda placement paper