what is the maximum load on for 10 kva & 25 kva transformer
Answer Posted / aruloli
Dear Friend
You forgot to furnish few more data i.e Voltage rating of
primary and secondary.
If i assume Voltage rating for 10 KVA Transformer as 230
V/110 V (Primary/secondary)and considering as single phase .
primary load current is calculated as
P=VI
10*1000(VA)=230*I
I=43.47 A
Secondary current is ,
90.90 A
Considering Transformer as 3 phase, then
P=1.732*v*I
Primary load current is
10000=1.732*230*I
I=25.10 A
Secondary is,
52.48 A
| Is This Answer Correct ? | 35 Yes | 15 No |
Post New Answer View All Answers
Tell me the reason of connecting domestic t/f primary in star or delta,and also secondary side.
What are the basic component of a cro?
What is the different types of cable & current capacity of cable
Where can i get practical knowledge of solar system?
why u r living from presentaly working.
wHAT IS CAPACITANCE LATCHING? hOW TO CALCULATE CAPACITANCE LATCHING? hOW TO SOLVE THE PROBLEM IF CAPACITANCE LATCHING APPLIED?
How to do fabrication , busbar and wiring cost for : 1. LT Panels 2. C& R Panel
Please explain, how to test vector group of tranformer(Delta y1) . Thank
how can i determine the KVA/MVA rating of transformer precisely?? is there any standard test?????
why lightning arrestor are made in two stack of insulator but why not cvt
any idea abt REVERSE METERING concept.........?
Is it possible to measure correct value of earth resistance & cable insulation ristance with out disconncting earth lead & both sides of cable ends? If not, any other method to measure ER & CIR with out disconneting from the system.
what is the use of Auto re-closer?
what is the minimum pay scale for electrical engineer (building construction)in kuwait? plz revert back with yrs of experience & pay scale respectively.
Usually in the L & T make MCC feeders' power circuit,we have BMR after the MAIN CONTACTOR.,can we interchange their position, keeping the control logic same???