How much KVAr bank reqired for 630 KVA transformer on full
load for maintain power factor upto.99
Answer Posted / dhanesh koshti
Capacitor calculation is depends on load. if 630 KVA transformer is loaded fully with load p.f.=1 then no compansation is required but if the same is fully loaded with load p.f. = 0.8 then, kvar required is calculated as below:
KVAR = KW ( tanǾ1-tanǾ2); Ǿ1=old p.f.angle, Ǿ2=new pf angle
= 504 ( 0.75 - 0.14) [ here, KW=504 because, 630 X 0.8 = 504]
= 307.44 KVAR
say, 300 KVAR bank is required at load end for compansation
| Is This Answer Correct ? | 15 Yes | 4 No |
Post New Answer View All Answers
how to Select Lighting arrester? What r the parameters to be considered for the selection of Lighting arrester ?
Is there any Institution for giving M-tech in Electrical engineering for those who r in service? Give the details please.
How the frame size of a flange mounted AC induction motor is calculated?
HOW WE KNOW IN PHYSICALLY THE CONTACT SURFACE OF A VACUUM INTERRUPTER IS GOOD OR GOING TO DAMAGE IN A VCB AFTER ABOVE 500 TIMES OPERATED.
What is the effect on in Zone and out zone fault if Phase side CT is Vk/2<30 mA and Neutral side is CT is Vk/4<30 mA for Transformer REF protection
send me any model test paper of clerical post of state bank of india.......
Rules and standards of electrical control wiring ?
How it can worked plc based electrical system And which type of software using.
briefly explain principle of resistance welding
how to size H.T & L.T Panel ?
How Diesel Generator start ?
when elecromagnatic waves are propogated in a wave guide?
What about electrical Units. discrive in detail
What is minimum phase system?
What determines the thickness of the lamination or stamping?